Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop B
Sequence Number 6
Notes
Date Text
2008-03-04 19:40:05BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 3RD REVIEW OF REVISION FOR INCREASE IN NUMBER OF
 STORIES FROM 5 TO 8 STORIES.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 9/23/07:
  
 3)IMPACT FEES. THE PROPOSED INCREASE IN BUILDING AREA
 WILL INCREASE THE IMPACT FEES DUE.THE PLANS SHALL BE
 TAKEN TO PALM BEACH COUNTY BUILDING DEPARTMENT FOR
 CALCULATION OF THE ADDITIONAL IMPACT FEES. THEY SHALL
 BE STAMPED AT THAT OFFICE AND A COPY OF THE PAID
 RECEIPT SUBMITTED TO THE CITY OF WEST PALM BEACH DEPT
 OF CONSTRUCTION SERVICES BEFORE THE REVISED PLANS CAN
 BE STAMPED.
  
 4) FBC TABLE 500ALLOWABLE BUILDING HEIGHT.FBC
 503.2.6 STATES THAT THE HEIGHT OF RESIDENTIAL
 OCCUPANCY, IN BUILDINGS OF TYPE II CONSTRUCTION, CAN BE
 UNLIMITED PROVIDED THE FIRE RESISTANCE OF ALL COLUMNS
 IS NOT LESS THAN 3 HOURS.YOUR COMMENT RESPONSE LETTER
 HAS BEEN NOTED.STEEL COLUMNS: SHEET A-506 HAS BEEN
 REVISED TO SHOW THE UL SYSTEM FOR FIRE RESISTANCE
 RATING OF THE STEEL COLUMNS, BUT THE APPLICATION
 THICKNESS TABLE REPRODUCED ON THE PLANS IS NOT LEGIBLE.
 SHOW A LEGIBLE TABLE ON THE PLANS.ALSO, THE TABLE
 COVERS MANY DIFFERENT FIRE RESISTANCE RATINGS, SOME OF
 WHICH ARE LESS THAN 3 HOURS.THE PLANS SHALL CLEARLY
 STATE, FOR THE CONTRACTOR AND INSPECTOR, THAT A 3 HOUR
 FIRE RESISTANCE RATING IS REQUIRED FOR THE COLUMNS ON
 THIS PROJECT.CONCRETE COLUMNS: THE COMMENT RESPONSE
 LETTER STATES THAT THE COLUMN FIRE RESISTANCE RATING
 HAS BEEN PROVIDED PER SECTION 709.2.1.1.1 OF FBC 2001.
 THAT SECTION IS ACTUALLY FOR WALLS.THE APPLICABLE
 SECTION FOR COLUMNS IS 709.2.4 OF FBC 2001 WHICH
 REQUIRES A MINIMUM CONCRETE COLUMN DIMENSION OF 12
 INCHES FOR A 3 HOUR FIRE RESISTANCE RATING, OR A
 MINIMUM CONCRETE COLUMN DIMENSION OF 8 INCHES IF TWO
 PARALLEL SIDES ARE AT LEAST 36 INCHES LONG.COLUMN
 TC-5, SHOWN ON SHEET S-9, DOES NOT COMPLY WITH EITHER
 REQUIREMENT OPTION.REVISE THE SIZE OF COLUMN TC-5 TO
 COMPLY WITH SECTION IS 709.2.4 OF FBC 2001
  
 13) FBC 13-103.1.2THIS COMMENT HAS STILL NOT BEEN
 ADDRESSED.THE SUBMITTED REVISED ENERGY CODE
 COMPLIANCE FORM SHALL BE SIGNED (ON PAGE 2) BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER. ALSO,
 THREE SIGNED AND SEALED COPIES OF THE ENERGY CODE
 COMPLIANCE FORM ARE REQUIRED BUT ALL THREE SUBMITTED
 COPIES HAVE A PHOTOCOPY OF RAFAEL PENA'S SIGNATURE, AND
 TWO ARE NOT SEALED.THE SIGNATURE MUST BE ORIGINAL AND
 THE SEAL MUST BE AFFIXED.
  
 15) FBC 1606.1WIND LOADS ON PARKING STRUCTURE.THE
 SUBMITTAL FOR THE HARDING STEEL, INC. PARKING STRUCTURE
 DOES NOT INCLUDE ANY WIND LOAD DESIGN CRITERIA.THE
 STRUCTURE MUST BE DESIGNED TO WITHSTAND A WIND SPEED OF
 140 MPH (3 SECOND GUST).SUBMIT WIND LOAD DESIGN
 CRITERIA/CALCULATIONS.ALL STRUCTURAL SUBMITTALS MUST
 BE REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD FOR
 THE PROJECT AND INCLUDE THE SHOP DRAWING REVIEW STAMP
 OF THAT ENGINEER.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS