Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop M
Sequence Number 5
Notes
Date Text
2007-08-05 12:33:49---------------DENIED------------------
  
 2ND REVIEW OF REVISIONS.
  
 FBC 2001 CODE FAMILY.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF
 CONTINUITY.
  
 1. OK
  
 2. THE 4 INCH ROUND DRYER DUCT IS PENETRATING A RATED
 WALL INTO SUITE 210. HOW WILL THIS DUCT PENETRATION BE
 PROTECTED? ACCORDING TO FINISH SCHEDULE ON A-602, THE
 LAUNDRY ROOM HAS NO CEILING OTHER THAN THE EXPOSED
 CONCRETE FROM THE DECK ABOVE. IT DOES NOT MEET
 EXCEPTION (3)(4) UNDER FBC,M 607.1.3. SHOW HOW THE FIRE
 RESISTANCE RATING OF THE WALL IS TO BE MAINTAINED PER
 FBC,M 504.2.
  
 3. PROTECTION OF SHAFT AT BOTTOM IS NOW SHOWN ON CSR-1,
 BUT NONE IS SHOWN ON SER-1. PLEASE CORRECT.
  
 4. OK
  
 5. OK, EXCEPT FOR THE ISSUE AS STATED IN COMMENT #3.
  
 6. THE DISTANCE REQUIRED FOR SEPARATION OF INTAKE
 OPENINGS FROM SOURCES OF CONTAMINATION IS TO BE
 MEASURED HORIZONTALLY. NO PROVISIONS IS MADE IN THE
 CODE FOR INTAKE OPENINGS TO BE DIRECTLY ABOVE SOURCES
 OF CONTAMINATION GIVEN A CERTAIN ELEVATION DIFFERENCE.
 EXAMPLE: WHAT IF A LARGE TRUCK WITH VERTICAL EXHAUST
 PIPES WAS PARKED IN THE ALLEY UNDER THE INTAKE
 OPENING?
  
 7.PROVIDE DETAIL IN ACCORDANCE WITH THE FIRE WRAP
 MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING
 WRAPPED DUCT PENETRATION OF THE RATED ENCLOSURE AND HOW
 THE FIRE WRAP IS TO TERMINATE AT THIS LOCATION.
  