| Plan Review Notes For Permit 05031185 |
| Permit Number |
05031185 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-03-04 13:16:29 | ***DENIED*** | | | | | | PLEASE NOTE THAT SOME OF THE COMMENTS HAVE BEEN | | | ADDRESSED. A RESPONSE LETTER WAS SUBMITTED REFERRING | | | REVIEWERS TO THE MEP ENGINEER. I WAS UNABLE TO LOCATE | | | THE LETTER SPECIFIC TO THE FIRE REVIEW COMMENTS. | | | | | | 1) OK | | | | | | 2) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 3) RESPONSE REFERS TO CIVIL ENGINEER'S RESPONSE. | | | | | | 4) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 5) OK | | | | | | 6) OK | | | | | | 7) OK | | | | | | 8) OK | | | | | | 9) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 10) SMOKE DETECTORS ARE STILL NOT SHOWN IN CORRIDOR | | | 142. | | | | | | 11) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 12) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 13) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | 14) RESPONSE REFERS TO ENGINEER'S RESPONSE. | | | | | | I UNDERSTAND THAT SOME COMMENTS MAY BE THE | | | RESPONSIBILTY OF DIFFERENT INDIVIDUALS, BUT IT WOULD | | | HELP EXPEDITE THIS PROCESS IF RESPONSES WERE | | | CONSOLIDATED AND PROVIDED WITH THE SUBMITTAL AT ONE | | | TIME. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|