Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop E
Sequence Number 5
Notes
Date Text
2008-02-06 19:23:232008-02-06 19:23:23
  
 ** DENIED REVISIONS FOR THIRD REVIEW **
  
 CLARKES HOTEL
 REVISIONS FROM PREVIOUS PERMITTED 5 STORY TO 8-STORY
 HIGH RISE.
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE SOME NEW COMMENTS BASED ON NEW SUBMITTED
 DOCUMENTS NOT PREVIOUSLY SUBMITTED FOR REVIEW. PLEASE
 SEE SOME OF THE SAME EXACT SHEETS THIS REVIEWER
 PERSONALLY REDLINED FROM PREVIOUS REVIEW WERE SUBMITTED
 BACK IN NEW SETS WITHOUT ANY CHANGES.
 THIS REVIEWER HAS PLACED DIRECT PHONE NUMBER AND E-MAIL
 ADDRESS ON ALL PREVIOUS REVIEWS AND NO CONTACT WAS MADE
 TO GO OVER ANY OF THESE ITEMS SINCE THE LAST REVIEW.
  
  
  
 1) NOTE:AS REQUESTED ON ALL PREVIOUS REVIEWS:PLEASE
 SUBMIT ALL THE MANUFACTURE SPECS/CUT SHEETS FOR ALL OF
 THE FOLLOWING. PLEASE SUBMIT FOR; FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, FUEL TANK. (SEENOTES BELOW),
 ATS EQUIPMENT (SEENOTES BELOW). 110.3, 90.7.PLEASE
 KNOW AT THIS TIME THERE ARE SEVERAL ITEMS WHICH REMAIN
 UNANSWERED FOR REQUIRED CODE ITEMS AND COORDINATION OF
 PLANS WITH OUT THESE ITEMS.
 PLEASE SEE THERE ARE SEVERAL ITEMS IN NFPA-110 AND
 NFPA-20 WHICH CAN NOT BE REVIEWED FOR COMPLIANCE AND
 COORDINATION WITHOUT THESE DOCUMENTS BEING SUBMITTED.
  
 2) NOTE: AS REQUESTED ON ALL PREVIOUS REVIEW:PLEASE
 SUBMIT COMPLETE PHOTO-METRICS FOR ALL EGRESS PATHS
 WHICH MEET THE MINIMUM LIFE SAFETY CODE7.8.1.3,
 7.9.2.2. THE MINIMUM LEVELS UNDER THE THESE SECTIONS
 REQUIRE 10FT CANDLE MIN FOR STAIRS UNDER NORMAL AND 1FT
 CANDLE UNDER EMERGENCY.
 PLEASE SEE FOR EXAMPLE EGRESS STAIRS A SPECIFICALLY
 MENTIONED ON PREVIOUS REVIEWS WHICH STILL SHOW LESS
 THAN THE MINIMUM OF 10FT CANDLES UNDER NORMAL. PLEASE
 SEE SHEET E-4A WHICH IS THE SAME EXACT SHEET WHICH WAS
 PREVIOUSLY SUBMITTED. THIS SHEETS STILL CONTAINS
 REDLINES BY REVIEWER ALONG WITH NEW REDLINES TO HELP
 RESOLVE.
 PREVIOUS REVIEW ALSO MENTIONED TO SHOW LEVELS UNDER
 BOTH EMERGENCY AND NORMAL.
 PREVIOUS REVIEWS ALSO REQUESTED COORDINATION BETWEEN
 FIXTURES FROM THE PHOTO-METRICS TO LIGHTING PLANS FOR
 FIXTURE TYPES. FOR EXAMPLE: PLEASE SEE THE SAME EXACT
 SHEETS FOR SHEET E-1 WERE SUBMITTED BACK WITH THIS
 REVIEWERS SAME REDLINED FIXTURES WHICH CLEARLY SHOW HE
 AND DE FIXTURES ON LIGHTING PLANS AND YET THE SAME
 SHEET FOR THE SAME FIXTURES ON THE PHOTO-METRICS
 INDICATE FE AND EE FIXTURES. HOW IS THIS POSSIBLE?
 WHICH FIXTURES ARE PROPOSED?
 PLEASE SEE FAC 61G15-33.004. THIS SECTION OF THE
 FLORIDA ADMINISTRATIVE CODE IS WITH RESPECT TO MINIMUM
 REQUIREMENTS FOR LIGHTING DESIGN BY THE ENGINEERING
 PROFESSIONAL.
  
 3) NOTE: PLEASE KNOW BASED ON THE NEW ELECTRICAL DATA
 SUBMITTED FOR THE PARKING LIFT SYSTEM, ALL EQUIPMENT
 MUST BE LISTED ASSEMBLY. THE DOCUMENTS CLEARLY STATE UL
 LISTED COMPONENTS OR PARTS, HOWEVER COULD NOT LOCATE
 ANY LISTING FOR SYSTEM CONTROL PANELS ETC.
 PLEASE SUBMIT LISTED SYSTEM DOCUMENTS OR KNOW THE
 SYSTEM WILL BE REQUIRED TO BE LISTED BY A NRTL(
 NATIONALLY RECOGNIZED TESTING LABORATORY) BEFORE FINAL.
 THIS WOULD INCLUDE ALL INSTALLED AT RISK WITH *PROVISO*
 TO OBTAIN LISTINGS.
 110.3
  
 4) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSES THE
 LIGHTNING PROTECTION SYSTEM NOTED ON PLANS WILL BE
 REQUIRED TO BE SUBMITTED UNDER SEPARATE PLANS AND
 PERMIT.
 ALL WORK SHALL BE PER NFPA-780 AND MASTER LABEL SHALL
 ALSO BE MADE AVAILABLE TO THE CITY FOR RECORD PLANS.
  
 5) NOTE: PLEASE SEE NO REVISED FBC ENERGY CALCULATIONS
 WERE SUBMITTED AS REQUIRED PER FBC CHAPTER 13. PLEASE
 KNOW AS THE FIXTURES HAVE CHANGED AND ENERGY
 CONSUMPTION HAS CHANGED, THIS WILL AFFECT THE
 STRUCTURE. PLEASE SUBMIT THESE ENERGY CALCULATIONS
 BASED ON THE 2001 CODE WHICHIS WHAT THIS PROJECT IS
 PERMITTED UNDER.
 FBC CHAPTER 13, 13-400.1.A, 13-415.2 ETC
  
 6) NOTE: PLEASE VERIFY THE SMOKE DEVICES IN UNITS ARE
 IN FACT SMOKE DETECTORS AS SHOWN OR SMOKE ALARMS PER
 NFPA-72. PLANS CAME BACK STILL SHOWING THESE AS SMOKE
 DETECTORS. IF THESE DEVICES DETECT SMOKE AND SOUND AN
 ALARM FROM THE UNIT ITSELF THEN THIS IS A SMOKE *ALARM*
 AND NOT DETECTOR. A SMOKE DETECTOR ONLY DETECTS AND
 DOES NOT SOUND AN ALARM. BASED ON PLANS AND DESIGN, IF
 THESE WERE SMOKE DETECTORS, EACH UNIT WOULD REQUIRE A
 FIRE ALARM PANEL.
 PLEASE CALL TO GO OVER THIS IF THERE ARE STILL ANY
 QUESTIONS.
  
 7) NOTE: AS REQUESTED ON ALL PREVIOUS REVIEWS: PLEASE
 SUBMIT THE REVISED FIXTURE SCHEDULE/LEGEND WHICH IS NOT
 ON ELECTRICAL PLANS. PLEASE BE SURE TO COORDINATE ALL
 INFORMATION ON THE FIXTURE LEGEND WITH THAT OF THE
 INPUT DATA REPORT ON UPDATED ENERGY CALCULATIONS TO BE
 SUBMITTED.
 ORIGINAL PLANS CLEARLY DID CONTAIN THE INFORMATION AND
 WAS REMOVED.
 FBC CHAPTER 13, NFPA-101, NFPA-70 ETC
 FBC 104.1.2
  
 8) NOTE:THIS NOTE IS FOR INFORMATION ONLY: PLEASE
 KNOW BASED ON THE OCCUPANCY USE AT THIS TIME NEWLY
 PASSED HOUSE BILL 7121 DOES NOT APPLY HOWEVER GIVEN
 INFORMATION AT THIS TIME IF THE USE WAS TO CHANGE FROM
 HOTEL TO CONDOS, THEN HB 7121 WOULD APPLY.
 THIS IS ONLY NOTED FOR INFORMATION ONLY AND NO CHANGE
 NEEDS TO MADE TO PLANS FOR CURRENT USE.
  
 9) NOTE: AS STATED ON THE PREVIOUS REVIEW:PLEASE SEE
 NFPA-110 CHAPTER 7,7.2.3 FOR MIN ELEVATION REQUIRED
 FOR ALL EPSS EQUIPMENT INCLUDING GEN.
 PLEASE PROVIDE MIN LEVELS FOR "SLOSH" ( SEA, LAKE,
 OVERLAND , SURGES, BY HURRICANES) CHARTS BASED ON A CAT
 4 STORM OR THE 100YR ELEVATION ON PLANS.
 THE RESPONSE MENTIONS, BUILDING LOCATED ABOVE FLOOD
 LEVEL. PLEASE KNOW HOWEVER THE MINIMUM LEVEL FOR EPSS
 EQUIPMENT BASED ON THE CHARTS NOTED ABOVE NEEDS TO BE
 STATED AND SHOWN ON PLANS. PLEASE SEE NO ELEVATIONS ON
 ELECTRICAL PLANS FOR LIFE SAFETY EQUIPMENT IS BEING
 SHOWN. (FIRE PUMP ON MEZZANINE LEVEL IS NOT NEEDED) AS
 THIS IS A GIVEN DUE TO ITS LOCATION.
 SAME NOTE:
  
 10) NOTE:PLEASE SEE THE GROUNDING ELECTRODE FOR THE
 FIRE PUMP SERVICE HAS NOW BEEN REMOVED??
 PREVIOUS NOTE WAS WITH RESPECT TO THE SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR BEING TOO SMALL AND NOW
 IT CAN NOT BE LOCATED?
 PLEASE ALSO SEE THE FEEDER SCHEDULE INDICATES AN
 *EQUIPMENT GROUNDING CONDUCTOR* NOW FROM THE FPL
 TRANSFORMER TO THE FIRST MEANS OF DISCONNECT WHICH IS
 NOT PERMITTED PER 250.6 AND 250.24.
 PLEASE CALL TO GO OVER THIS SCENARIO IN ORDER TO MAKE
 THE NEEDED ADJUSTMENTS.
 PLEASE SEE 250.50, 250.66 ETC
  
 11) NOTE: PLEASE SEE THE FUEL TANK IS NOW SHOWN AS 400
 GALLONS ON THE FUEL CALCULATIONS AND 500 GALLONS ON
 RISER UNDER GENERATOR?
 WHICH ONE IS IT?
 PLEASE SEE NOTES ABOVE WITH RESPECT TO THE SUBMISSION
 OF MANUFACTURES SPECS/CUT SHEETS.
 FBC 104.1.2 FOR COORDINATION OF PLANS.
  
 12) NOTE: PLEASE SEE THE FP SHEETS SHALL STATE THE CODE
 RELEVANT FOR DESIGN. THIS COULD BE REDLINED IF THIS WAS
 THE ONLY COMMENT ON SHEET FP-1 THIS SHOULD REFLECT 1999
 NFPA-20 ( CAN NOT BE LATEST EDITION AS THERE IS MOST
 CERTAINLY ONE NEW NFPA-20ALREADY ADOPTED BY THE STATE
 AND WILL HAVE ANOTHER NEW CODE ADOPTED BY THE STATE
 BEFORE FINAL.
  
 13) NOTE: AS REQUESTED ON PREVIOUS REVIEWS: THIS
 COMMENT WILL REMAIN AS THE INFORMATION WHICH WILL BE
 SUBMITTED ON GENERATOR WILL CONFIRM AVAILABLE FAULT
 CURRENT ON THE GENERATOR. THE LEVELS ON THE MANUFACTURE
 SPECS/CUT SHEETS WILL ALSO BE REVIEWED.
 PLEASE PROVIDE ALL AIC RATINGS FOR ALL EQUIPMENT, ATS,
 DISCONNECTS ETC. PLEASE SEE 701.6, NFPA-20 6-3.2.2.4,
 110.9, 240.12 ETC. PLEASE SEE NFPA-110 6.5.2 ETC.
 PLEASE BE SURE ALL EQUIPMENT/MANUFACTURE SPECS/CUT
 SHEETS SHOWS THIS COORDINATION.
 THE MOST IMPORTANT PART OF THIS COMMENT IS THE
 SELECTIVE COORDINATION REQUIRED FOR LIFE SAFETY SYSTEMS
 AS NOTED ON PREVIOUS REVIEW PER 240.12 OF THE NEC AND
 OTHER SECTIONS OF NFPA-110 ETC
 PLEASE SUBMIT THE SELECTIVE COORDINATION STUDY FOR THE
 REQUIRED AND LIFE SAFETY SYSTEMS.
 FAC 61G15-33.003
 FBC 104.1.2 FOR ADDITIONAL INFORMATION.
  
 14) NOTE:PLEASE SEE PREVIOUS REVIEWS REQUESTED THE
 MINIMUM LEVELS FOR ADA COMPLIANCE WITH RESPECT TO HORN
 AND STROBE LEVELS. THE PLANS DO NOT SHOW ALL LEVELS,
 HOWEVER SYMBOL LEGEND WAS REVISED FOR STROBE LEVELS.
 THE NOTES HOWEVER FOR HORN AND SOUND LEVELS STATE
 LEVELS SHALL MEET NFPA-72. THIS IS TRUE TO A POINT AS
 THEY ARE REQUIRED TO MEET THE MINIMUM LEVELS PER
 NFPA-72 HOWEVER THE LEVELS PER THE FBC ARE MORE
 RESTRICTIVE WHICH WOULD APPLY.
 PLEASE ADJUST LEVELS AND NOTES.
 SECTIONS GIVEN IN PREVIOUS REVIEWS: PLEASE PROVIDE ALL
 MINIMUM AUDIBLE AND VISUAL LEVELS PER FBC 2001 11-4.28,
 11-4.28.2 AND MOST IMPORTANT 11-4.28.3(4). ALL AREA AS
 STATED IN 11-4.28.1 SHALL BE NOTED AND INCLUDED.
  
 15) NOTE: PLEASE KNOW A RESPONSE LETTER FROM DESIGN
 TEAM IS NOT REQUIRED HOWEVER DOES HELP IN THE REVIEW
 PROCESS. AS CONTACT WAS NOT MADE WITH THIS OFFICE SINCE
 LAST REVIEW PLEASE SEE NOTE BELOW.
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]