2007-09-23 19:46:24BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 2ND REVIEW OF REVISION FOR INCREASE IN NUMBER OF
 STORIES FROM 5 TO 8 STORIES.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 12/10/06:
  
 1) FBC* 104.6.5BUILDING PERMIT VALUATION.THE
 PROPOSED INCREASE IN BUILDING AREA WILL INCREASE THE
 VALUE OF THE PROJECT FOR PERMIT FEE CALCULATION
 PURPOSES.THE VALUE CURRENTLY STATED IS $5,362,279 AND
 THE FEES PAID TO DATE WERE BASED ON THAT VALUE.THE
 VALUE, CALCULATED USING THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL (SBCCI) VALUATION TABLES FOR THE
 PROPOSED INCREASED BUILDING AREA, IS $8,268,362.IN
 ORDER TO PROCEED WITH THE PROPOSED REVISION, THE PERMIT
 APPLICATION FEE WOULD HAVE TO BE ADJUSTED ACCORDINGLY,
 SO THERE WOULD BE AN OUTSTANDING BALANCE OF $32,257.53.
 THIS ADDITIONAL FEE AMOUNT WILL HAVE TO BE PAID BEFORE
 THE PLANS REVISED PLANS CAN BE STAMPED.
  
 2) RADON FEES.THE PROPOSED INCREASE IN BUILDING AREA
 WILL INCREASE THE RADON FEES.THE RADON FEES PAID TO
 DATE AMOUNT TO $532.96.THE TOTAL RADON FEES FOR THE
 PROPOSED BUILDING AREA WOULD BE $799.72.THE
 DIFFERENCE IS $266.76 AND THIS AMOUNT WOULD HAVE TO BE
 PAIDBEFORE THE REVISED PLANS CAN BE STAMPED.
  
 3)IMPACT FEES. THE PROPOSED INCREASE IN BUILDING AREA
 WILL INCREASE THE IMPACT FEES DUE.THE PLANS SHALL BE
 TAKEN TO PALM BEACH COUNTY BUILDING DEPARTMENT FOR
 CALCULATION OF THE ADDITIONAL IMPACT FEES. THEY SHALL
 BE STAMPED AT THAT OFFICE AND A COPY OF THE PAID
 RECEIPT SUBMITTED TO THE CITY OF WEST PALM BEACH DEPT
 OF CONSTRUCTION SERVICES BEFORE THE REVISED PLANS CAN
 BE STAMPED.
  
 4) FBC TABLE 500ALLOWABLE BUILDING HEIGHT.CONTRARY
 TO THE SUBMITTED RESPONSE LETTER, THE ARCHITECTURAL
 PLANS DO NOT SHOW THAT THE COLUMNS WILL HAVE 3-HOUR
 FIRE RESISTANCE RATING.THERE IS NO NOTE IN THE
 ARCHOTECTURAL OR STRUCTURAL PLANS STATING THAT THE
 COLUMN FIRE RESISTANCE RATING IS 3-HOURS.NO "VOIDED"
 (PREVIOUSLY REVIEWED) STRUCTURAL SHEETS, AND NOT ALL
 "VOIDED" ARCHITECTURAL SHEETS, WERE SUBMITTED FOR
 COMPARISON WITH THE PROPOSED PLANS, AND SHEETS S-1 AND
 S-2 DO NOT INDICATE ANY CHANGE TO THE COLUMN SIZES.
 3-HOUR FIRE RESISTANCE RATED COLUMNS ARE REQUIRED
 THROUGHOUT THE BUILDING BECUSE FOR RESIDENTIAL
 OCCUPANCY (INCLUDING R-1 HOTEL) THE MAXIMUM HEIGHT OF A
 BUILDING OF TYPE II CONSTRUCTION IS 80 FEET UNLESS
 FOOTNOTE (A) ALLOWS HEIGHT MODIFICATION. FOOTNOTE
 (A)(7) REFERS TO FBC 503.2.6 FOR RESIDENTIAL OCCUPANCY.
 FBC 503.2.6 STATES THAT THE HEIGHT OF RESIDENTIAL
 OCCUPANCY, IN BUILDINGS OF TYPE II CONSTRUCTION, CAN BE
 UNLIMITED PROVIDED THE FIRE RESISTANCE OF ALL COLUMNS
 IS NOT LESS THAN 3 HOURS. THE PROPOSED HEIGHT OF THE
 BUILDING DOES EXCEED 80 FEET, SO THE PLANS MUST BE
 AMENDED TO SHOW ALL COLUMNS TO HAVE A FIRE RESISTANCE
 RATING OF NOT LESS THAN THREE HOURS.
  
 6) FBC 412.6.1ELEVATOR LOBBY DOORS ARE REQUIRED TO
 HAVE A 20-MINUTE FIRE-RESISTANCE RATING.THE NOTE
 ADDED TO SHEET A-125 DOES SHOW A REQUIREMENT FOR A
 20-MINUTE FIRE RESISTANCE RATED DOOR AT THE ELEVATOR
 LOBBY/CORRIDOR BUT IT HAS NO ANNOTATION AT THE ELEVATOR
 LOBBY/VESTIBULE.ALSO, THE DOOR SCHEDULE HAS NOT BEEN
 UPDATED TO CORRELATE WITH THIS REQUIREMENT.DOORS
 299D, 299E, 399C, 399E, 499C, 499E, 599C, 599E, 699C,
 699E, 799C, 799E, 899C AND 899E ARE ALL REQUIRED TO BE
 20-MINUTE DOORS.THE DOOR SCHEDULE ON SHEET A-604 DOES
 NOT SHOW THESE DOORS AS FIRE RESISTANCE RATED.AMEND
 THE DOOR SCHEDULE TO CLEARLY SHOW THE REQUIRED FIRE
 RESISTANCE RATINGS FOR THESE DOORS.20-MINUTE FIRE
 RESISTANCE RATED DOORS ARE REQUIRED BECAUSE THE
 BUILDING AS REVISED WILL BE CLASSIFIED AS 'HIGH RISE'
 BECAUSE IT WILL HAVE OCCUPIED FLOORS MORE THAN 75 FEET
 ABOVE FIRE DEPARTMENT ACCESS LEVEL.1-HOUR FIRE
 RESISTANT ELEVATOR LOBBIES, WITH 20-MINUTE LOBBY DOORS,
 ARE REQUIRED ON ALL FLOORS ABOVE THE MAIN ENTRANCE
 LEVEL.
  
 11) FBC 11-4.1.3(5)ELEVATOR ACCESS TO ROOF UPPER
 DECK.IT IS NOTED THAT SHEET A-111 HAS BEEN REVISED TO
 SHOW AN ACCESSIBLE RAMP FROM THE UPPER DECK TO THE
 LOWER DECK.HOWEVER, NO DETAILS HAVE BEEN SUBMITTED TO
 SHOW COMPLIANCE WITH RAMP SLOPE, LANDING AND HANDRAIL
 REQUIREMENTS.
  
 13) FBC 13-103.1.2THIS COMMENT HAS NOT BEEN
 ADDRESSED.THE SUBMITTED REVISED ENERGY CODE
 COMPLIANCE FORM SHALL BE SIGNED (ON PAGE 2) BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER. ALSO,
 THREE SIGNED COPIES OF THE ENERGY CODE COMPLIANCE FORM
 ARE REQUIRED.
  
 14) FBC* 104.2.1CROSS-SECTIONS A-302/B-B AND
 A-304/D-D HAVE NOT BEEN UPDATED TO REFLECT THE FACT THE
 THAT ELEVATOR STOPS AT THE UPPER DECK LEVEL AND THAT
 THERE IS NOW AN ACCESSIBLE RAMP FROM THE UPPER DECK TO
 THE LOWER DECK.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS