| 2007-09-13 14:16:45 | ***DENIED*** |
| | |
| | PLEASE NOTE THAT THIS PROJECT HAS CHANGED FROM FIVE (5) |
| | STORIES TO EIGHT (8) STORIES, AND SHALL MEET ALL |
| | REQUIREMENTS OF NFPA 101, CHAPTER 11 FOR HIGHRISE |
| | BUILDINGS. |
| | |
| | 1) HIGHRISE BUILDINGS SHALL BE PROVIDED WITH AS MINIMUM |
| | OF TWO (2) FIRE DEPARTMENT CONNECTIONS WITH KNOX |
| | LOCKING CAPS. PLANS DO SHOW (2) CONNECTIONS. |
| | |
| | 2) FIRE ALARM SYSTEM TO MEET SURVIVABILITY |
| | REQUIREMENTS. |
| | |
| | 3) PLEASE PROVIDE A CLEAR DETAIL REGARDING SUPERVISING |
| | EQUIPMENT ON DOUBLE DETECTOR CHECK ASSEMBLY. SHEET C-8 |
| | |
| | 4) PLANS CALL OUT KNOX BOXES WITH LOCKING CAPS. PLEASE |
| | CLARIFY AND CORRECT AS LOCKING CAPS WOULD BE REQUIRED |
| | FOR FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 5) PLEASE ADD INFORMATION REGARDING ACCESS OR NO ACCESS |
| | TO ROOF ON STAIRWELL TACTILE SIGNAGE. |
| | |
| | 6) LIFE SAFETY SHEETS ILLUSTRATE THE FIRE RATING OF |
| | SOME DOORS. PLEASE INDICATE THE FIRE RATING OF THE DOOR |
| | TO THE FIRE COMMAND ROOM. |
| | |
| | 7) PLEASE PROVIDE FIRE RATING OF DOORS TO THE PUMP |
| | ROOM, GENERATOR ROOM AND ELECTRICAL ROOM. SHEET A-124 |
| | |
| | 8) EXIT SIGNS SHALL NOT SPAN A DISTANCE GREATER THAN |
| | 100'. |
| | |
| | 9) FIRE COMMAND ROOM STILL DOES NOT SHOW A SMOKE |
| | DETECTOR. SHEET FA-1 |
| | |
| | 10) SMOKE DETECTORS ARE NOT SHOWN IN CORRIDOR 142. |
| | PLEASE ADVISE IF THAT AREA IS PART OF THIS SCOPE OF |
| | WORK. |
| | |
| | 11) SMOKE/PRESSURIZATION AND VENTILATION INDICATES THAT |
| | SYSTEM IS SIZED FOR MAX. OF (5) STORIES. PLEASE ADVISE |
| | NOW THAT PROJECT IS (8) STORIES. |
| | |
| | 12) PLEASE CONTACT THE BUREAU OF FIRE PREVENTION |
| | REGARDING THE SMOKE MANAGEMENT PANEL. THE DRAWING ON |
| | SHEET AC-8 APPEARS TO NEED MORE DETAIL. PLEASE CALL |
| | (561) 804-4724 TO PROVIDE A DRAWING FOR REVIEW BY THIS |
| | OFFICE. |
| | |
| | 13) FIRE ALARM AND FIRE SPRINKLER PLANS WILL NEED TO BE |
| | UPDATED ILLUSTRATING NEW BATTERY CALCULATIONS AND |
| | SPRINKLER MODIFICATION FOR NEW PROPOSED FLOORS AT TIME |
| | OF PERMIT APPLICATION FOR REFERENCED SYSTEMS. |
| | |
| | 14) KNOX BOX AND LOCKING CAP APPLICATIONS MAY BE |
| | OBTAINED AT THE BUREAU OF FIRE PREVENTION. (561) |
| | 804-4724 |
| | |
| | PLEASE PROVIDE A RESPONSE LETTER TO FIRE PLAN REVIEW |
| | ADDRESSING THESE COMMENTS. IT WOULD BE HELPFUL TO |
| | INDICATE WHERE ON THE PLANS THE CHANGE IS ADDRESSED. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |