2006-10-26 18:03:48--------------DENIED---------------
  
 REVIEWED UNDER FBC 2001
  
 1. PG AC-7 TER 1,2,3 BATH FAN SUB DUCTS DO NOT MEET
 EXCEPTION #2 UNDER FBC,M 607.1.3. THE AIR IN THE RISER
 MUST BE TRAVELING UPWARD IN ORDER TO CLAIM THIS
 EXCEPTION. THE MAIN EXHAUST FANS ARE LOCATED ON THE
 MEZZANINE LEVEL CAUSING THE AIRFLOW TO BE DOWNWARD.
  
 2. PG AC-3 LAUNDRY ROOM DRYER EXHAUST DUCT CAN NEITHER
 PENETRATE THE SIDE NOR THE BOTTOM OF THE RATED SHAFT
 BEHIND LAUNDRY ROOM. WHEN A SUITABLE LOCATION FOR DRYER
 EXHAUST DUCT IS DETERMINED, PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.THIS IS ONLY
 REQUIRED IF THE DEVELOPED DUCT LENGTH EXCEEDS 25 FEET
 PER FBC,M 504.6.
  
 3. PG AC-7 SER 1 DUCT PENETRATIONS AT BOTTOM OF SHAFTS
 ARE REQUIRED TO BE PROTECTED PER FBC 705.2.3.3.
 MOTORIZED FIRE/SMOKE DAMPERS ARE RECOMMENDED IN THESE
 LOCATIONS AS A STANDARD FUSABLE LINK FIRE DAMPER HAS
 THE POTENTIAL TO RENDER THESE LIFE SAFETY COMPONENTS
 INOPERABLE.
  
 4. MANUAL VOLUME DAMPERS ARE NOT REQUIRED ON SMOKE
 EXHAUST DUCT SYSTEMS AND SHOULD BE REMOVED TO PREVENT
 POTENTIAL RESTRICTION OF AIRFLOW UNDER EMERGENCY
 CONDITIONS.
  
 5. PG AC-7 TWO RISERS ON THIS PAGE ARE LABELED "SER 1".
 PLEASE GIVE EACH RISER A DISTINCTIVE NAME FOR CLARITY.
  
 6. PG AC-2 INTAKE OPENING FOR SF1,AHU1,AHU3 IS IN A
 PROHIBITED LOCATION PER FBC,M 401.5.1.
  
 7. PG AC-2 GREASE EXHAUST DUCT SHALL BE ENCLOSED IN A
 RATED SHAFT PER FBC,M 506.3.12.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]