| 2006-10-26 18:03:48 | --------------DENIED--------------- |
| | |
| | REVIEWED UNDER FBC 2001 |
| | |
| | 1. PG AC-7 TER 1,2,3 BATH FAN SUB DUCTS DO NOT MEET |
| | EXCEPTION #2 UNDER FBC,M 607.1.3. THE AIR IN THE RISER |
| | MUST BE TRAVELING UPWARD IN ORDER TO CLAIM THIS |
| | EXCEPTION. THE MAIN EXHAUST FANS ARE LOCATED ON THE |
| | MEZZANINE LEVEL CAUSING THE AIRFLOW TO BE DOWNWARD. |
| | |
| | 2. PG AC-3 LAUNDRY ROOM DRYER EXHAUST DUCT CAN NEITHER |
| | PENETRATE THE SIDE NOR THE BOTTOM OF THE RATED SHAFT |
| | BEHIND LAUNDRY ROOM. WHEN A SUITABLE LOCATION FOR DRYER |
| | EXHAUST DUCT IS DETERMINED, PLEASE PROVIDE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS.THIS IS ONLY |
| | REQUIRED IF THE DEVELOPED DUCT LENGTH EXCEEDS 25 FEET |
| | PER FBC,M 504.6. |
| | |
| | 3. PG AC-7 SER 1 DUCT PENETRATIONS AT BOTTOM OF SHAFTS |
| | ARE REQUIRED TO BE PROTECTED PER FBC 705.2.3.3. |
| | MOTORIZED FIRE/SMOKE DAMPERS ARE RECOMMENDED IN THESE |
| | LOCATIONS AS A STANDARD FUSABLE LINK FIRE DAMPER HAS |
| | THE POTENTIAL TO RENDER THESE LIFE SAFETY COMPONENTS |
| | INOPERABLE. |
| | |
| | 4. MANUAL VOLUME DAMPERS ARE NOT REQUIRED ON SMOKE |
| | EXHAUST DUCT SYSTEMS AND SHOULD BE REMOVED TO PREVENT |
| | POTENTIAL RESTRICTION OF AIRFLOW UNDER EMERGENCY |
| | CONDITIONS. |
| | |
| | 5. PG AC-7 TWO RISERS ON THIS PAGE ARE LABELED "SER 1". |
| | PLEASE GIVE EACH RISER A DISTINCTIVE NAME FOR CLARITY. |
| | |
| | 6. PG AC-2 INTAKE OPENING FOR SF1,AHU1,AHU3 IS IN A |
| | PROHIBITED LOCATION PER FBC,M 401.5.1. |
| | |
| | 7. PG AC-2 GREASE EXHAUST DUCT SHALL BE ENCLOSED IN A |
| | RATED SHAFT PER FBC,M 506.3.12. |
| | |