| Plan Review Notes For Permit 05031185 |
| Permit Number |
05031185 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-31 14:27:34 | ***DENIED*** | | | | | | 1) FIRE SPRINKLER COVERAGE AND SUITE NUMBER APPEAR TO | | | BE MISSING IN AREA OFF COURTYARD 147. SHT FP-1 | | | | | | 2) SOME BATHROOMS ARE SPRINKLERED AND SOME ARE NOT. | | | PLEASE CLARIFY IF THIS IS BASED ON SQUARE FOOTAGE | | | DIFFERENCES OR JUST AN OVERSIGHT. | | | | | | 3) A SMOKE DETECTOR IS REQUIRED IN FIRE COMMAND ROOM IN | | | THE AREA OF THE FIRE ALARM CONTROL PANEL. | | | | | | 4) SMOKE MANAGEMENT PANEL SHALL PROVIDE A GRAPHIC | | | REPRESENTATION OF THE BUILDING. HOA SWITCHES WITH NO | | | OVERLAY OF THE BUILDING WILL NOT BE ACCEPTABLE. | | | | | | 5) FIRE AND SMOKE DAMPERS SHALL BE TESTED FOR CLOSURE | | | PRIOR TO FINAL INSPECTION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 OR (561) 804-4756 |
|