| Date |
Text |
| 2006-10-29 08:28:03 | ****UNSAT **** |
| | |
| | ** REVIEW FORE REVISION OF CLARKES HOTEL FROM 5-STORIES |
| | TO 8 STORIES. |
| | |
| | ** PLEASE KNOW THAT AT THIS TIME THERE IS NOT ENOUGH |
| | INFORMATION SUBMITTED FOR A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE AS THE BUILDING HAS NOW BEEN CLASSIFIED AS A |
| | HIGH-RISE. PLEASE SEE ONLY SOME NOTES BELOW ARE NOTED |
| | FOR ITEMS NEEDED. |
| | |
| | 1) NOTE: PLEASE SEE THAT ALL REVISIONS ON PLANS SHALL |
| | BE DATED, CLOUDED/TRIANGLE NOTATIONS ACCORDINGLY. |
| | PLEASE SEE DATES AND REVISION NUMBERS SHOW A REV #1, |
| | HOWEVER THIS HAS BEEN REVISED AT LEAST THREE OR FOUR |
| | TIMES. HOW IS THIS FIRST REVISION?? |
| | |
| | ** PLEASE KNOW AS THIS BUILDING IS COMPLETELY CHANGING |
| | IN DESIGNATION; PLEASE PROVIDE A COMPLETE SET OF |
| | REVISED ELECTRICAL PLANS AS SUBMITTING FOR A NEW |
| | BUILDING. A FULL REVIEW WILL BE BASED ON THE SUBMITTED |
| | PLANS. |
| | |
| | 2) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES AT A |
| | MINIMUM ON PLANS. |
| | 2002 NFPA-72(DONE), 1999 NFPA-20, 2003 NFPA-101, 2002 |
| | NFPA-110. |
| | IT IS KNOW THAT THIS PROJECT CAME IN UNDER THE 2001 |
| | FBC. |
| | |
| | 3) NOTE: PLEASE SUBMIT ALL THE MANUFACTURE SPECS/CUT |
| | SHEETS FOR ALL OF THE FOLLOWING. PLEASE SUBMIT FOR; |
| | FIRE PUMP, FIRE PUMP CONTROLLER, GENERATOR, FUEL TANK. |
| | (SEENOTES BELOW), ATS EQUIPMENT (SEENOTESBELOW). |
| | 110.3, 90.7 |
| | |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS. (ALL CORRIDORS AND STAIR TOWERS) PLEASE |
| | SEE LS-1017.8.1.3, 7.9.2.2 10FT CANDLE MIN FOR STAIRS |
| | UNDER NORMAL AND 1FT CANDLE UNDER EM. |
| | |
| | ** PLEASE ALSO BE AWARE OF ZONING COMMENTS AS |
| | PHOTO-METRICS WILL ALSO BE REQUIRED FOR FUTURE PARKING |
| | GARAGE. |
| | |
| | 5) NOTE: PLEASE SEE ZONING COMMENTS, PLEASE SEE IF A |
| | GARAGE IS NOW REQUIRED, THIS WILL COMPLETELY CHANGE |
| | ELECTRICAL SERVICE AND ELECTRICAL SHEETS SUBMITTED. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS PLANS WHICH WERE RED-LINED |
| | FOR CIRCUITING OF ELEVATOR MACHINE ROOMS PER 620.23, |
| | 620.24 AND ASSOCIATED EQUIPMENT. THIS HAS NOT BEEN |
| | CORRECTED ON PLANS TO DATE. |
| | |
| | 7) NOTE: PLEASE SEE ALL FIXTURE SCHEDULE AND TYPE |
| | INFORMATION WHICH WAS ON PREVIOUS PLANS HAS BEEN |
| | REMOVED FOR EM FIXTURES? |
| | PLEASE SEE ALL OF THE FOLLOWING IN ORDER TO REVIEW FOR |
| | CODE COMPLIANCE SHALL BE PLACED BACK ON PLANS. |
| | LS 101 |
| | |
| | 8) NOTE: PLEASE SEE THAT NOW THAT A GENERATOR IS |
| | INSTALLED AND REQUIRED AND USE IS TO A HIGH-RISE, |
| | PLEASE SEE NFPA-20 6-6.2 AS THE MINIMUM FUEL REQUIRED |
| | FOR FIRE PUMP IS 8HRS AT 100%, AND 5% FOR EXPANSION AND |
| | 5% FOR SUMP. |
| | PLEASE SEE TANK AS SHOWN AND FUEL CALCULATIONS CAN NOT |
| | VERIFIED AS NO INFORMATION WAS SUBMITTED. |
| | |
| | 9) NOTE: PLEASE SEE NFPA-20 CHAPTER 6 AND 7 FOR FIRE |
| | PUMP, ASTHERE ARE TOO MANY SECTIONS TO BE LISTED FOR |
| | ITEMS NEEDED FOR REVIEW. |
| | |
| | 10) NOTE: PLEASE SEE NFPA-110 CHAPTER 7,7.2.3 FOR MIN |
| | ELEVATION REQUIRED FOR ALL EPSS EQUIPMENT INCLUDING |
| | GEN. |
| | PLEASE PROVIDE MIN LEVELS FOR "SLOSH" ( SEA, LAKE, |
| | OVERLAND , SURGES, BY HURRICANES) CHARTS BASED ON A CAT |
| | 4 STORM OR THE 100YR ELEVATION ON PLANS. |
| | |
| | 11) NOTE: PLEASE SEE POOL AREA PHOTO-METRICS ARE TO BE |
| | REVIEWED AND STAMPED BY THE PALM BEACH COUNTY HEALTH |
| | DEPARTMENT IF ANY SWIMMING WILL TAKE PLACE OR PERMITTED |
| | FROM DUSK TO DAWN. PLEASE KNOW THAT THE POOL WILL ALSO |
| | BE REQUIRED UNDER A SEPARATE PERMIT. |
| | IF NO SWIMMING , PLEASE PROVIDE NOTES ON THESE PLANS AT |
| | THIS TIOME, EVEN THOUGH THE POOL WILL BE UNDER A |
| | SEPARATE PERMIT. |
| | |
| | 12) NOTE: PLEASE SEE SOME SHEETS ARE MISSING TITLE |
| | BLOCK INFORMATION AS REQUIRED FOR ENGINEER. PLEASE SEE |
| | MISSING THE PRINTED NAME, PRINTED LICENSE # AND MISSING |
| | THE DATE WHEN PLANS WERE SIGNED AND SEALED. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002 |
| | |
| | 13) NOTE: PLEASE CORRELATE AND LABEL ALL MAINS ON |
| | SCHEDULES, RISER AND MAIN ELECTRICAL ROOM(S). PLEASE |
| | SEE SCHEDULES DO NOT CORRELATE WITH RISER, ETC. 230.2E |
| | ETC, |
| | |
| | 14) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL |
| | EQUIPMENT, ATS, DISCONNECTS ETC. PLEASE SEE 701.6, |
| | NFPA-20 6-3.2.2.4, 110.9, 240.12 ETC. PLEASE SEE |
| | NFPA-110 6.5.2 ETC. |
| | PLEASE BE SURE ALL EQUIPMENT/MANUFACTURE SPECS/CUT |
| | SHEETS SHOWS THIS COORDINATION. |
| | |
| | 15) NOTE: PLEASE SEE NEC 11.26 FOR MAXIMUM DISTANCE A |
| | GUTTER OR ANY OTHER EQUIPMENT SHALL PROTRUDE IN FRONT |
| | OF EQUIPMENT. (6") PLEASE SEE RISER AND PROVIDE A SIDE |
| | ELEVATION TO INDICATE IF EQUIPMENT WILL BE MOUNTED OUT |
| | FROM THE WALL. |
| | PLEASE ALSO SEE THE FOLLOWING COMMENT FOR SIZING GUTTER |
| | TO MAIN 2 AND 3 ON RISER. (SHOWN AS DIFFERENT MAINS ON |
| | OTHER SECTIONS OF PLANS SEE NOTE #13). |
| | |
| | 16) NOTE: PLEASE SEE 240.4C, AS THE SEC'S FROM FPL TO |
| | GUTTER SHALL BE RATED AT 1200A?S OR ABOVE. |
| | 90.4. |
| | |
| | 17) NOTE: PLEASE ALSO VERIFY THE SIZE OF THE GUTTER FOR |
| | MAINS #2 AND #3 ON RISER. PLEASE SEE 366. |
| | |
| | 18) NOTE: PLEASE SEE MISSING A DISCONNECTING MEANS |
| | REQUIRED FOR THE FEEDERS COMING FROM THE GENERATOR TO |
| | MEET 701.11(B)5. |
| | |
| | 19) NOTE: PLEASE PROVIDE DETAIL FOR VERTICAL CONDUCTOR |
| | SUPPORTS PER 300.19(A). |
| | |
| | 20) NOTE: PLEASE SEE NFPA-110 FOR ATS EPSS EQUIPMENT |
| | SECTION: 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED |
| | TO BE INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM |
| | WHERE TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) |
| | OF NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN |
| | EQUIPMENT ENCLOSURES. |
| | THIS DOES NOT APPEAR TO BE MET AT THIS TIME. |
| | |
| | 21) NOTE: PLEASE PROVIDE ALL MINIMUM AUDIBLE AND VISUAL |
| | LEVELS PER FBC 2001 11-4.28, 11-4.28.2 AND MOST |
| | IMPORTANT 11-4.28.3(4). ALL AREA AS STATED IN 11-4.28.1 |
| | SHALL BE NOTED AND INLCUDED. THIS COMMENT WAS NEVER |
| | UNDER ELECTRICAL REVIEW SCOPE ON PREVIOUS REVIEWS UNTIL |
| | RECENTLY. |
| | |
| | 22) NOTE: PLEASE INCLUDE A NOTE ON ROOF TOP PLANS WHICH |
| | WILL STATE THAT "ANY LIGHTNING PROTECTION SYSTEM TO BE |
| | INSTALLED SHALL MEET NFPA-780" OR WORDS TO THAT AFFECT. |
| | A SYSTEM IS NOT REQUIRED, HOWEVER THE NOTE IS,AS THERE |
| | ARE MANY SYSTEMS BEING "PROMOTED AND SOLD" IN THE STATE |
| | OF FLORIDA WHICH ARE STRICTLY NOT PERMITTEDAND MANY |
| | KNOWN SYSTEMS ARE ACTUALLY A HEALTH AND LIFE SAFETY |
| | HAZARD. PLEASE SEE ONLY IF IN NFPA-780. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED. PLEASE KNOW THERE MAY BE FUTURE COMMENTS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2006-10-29 06:55:15 | REVIEW IN PROGRESS |
| 2006-10-28 19:23:25 | ONE ROLL IN ELECTRICAL FOR REVIEW. |