Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-29 08:28:03****UNSAT ****
  
 ** REVIEW FORE REVISION OF CLARKES HOTEL FROM 5-STORIES
 TO 8 STORIES.
  
 ** PLEASE KNOW THAT AT THIS TIME THERE IS NOT ENOUGH
 INFORMATION SUBMITTED FOR A COMPLETE REVIEW FOR CODE
 COMPLIANCE AS THE BUILDING HAS NOW BEEN CLASSIFIED AS A
 HIGH-RISE. PLEASE SEE ONLY SOME NOTES BELOW ARE NOTED
 FOR ITEMS NEEDED.
  
 1) NOTE: PLEASE SEE THAT ALL REVISIONS ON PLANS SHALL
 BE DATED, CLOUDED/TRIANGLE NOTATIONS ACCORDINGLY.
 PLEASE SEE DATES AND REVISION NUMBERS SHOW A REV #1,
 HOWEVER THIS HAS BEEN REVISED AT LEAST THREE OR FOUR
 TIMES. HOW IS THIS FIRST REVISION??
  
 ** PLEASE KNOW AS THIS BUILDING IS COMPLETELY CHANGING
 IN DESIGNATION; PLEASE PROVIDE A COMPLETE SET OF
 REVISED ELECTRICAL PLANS AS SUBMITTING FOR A NEW
 BUILDING. A FULL REVIEW WILL BE BASED ON THE SUBMITTED
 PLANS.
  
 2) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES AT A
 MINIMUM ON PLANS.
 2002 NFPA-72(DONE), 1999 NFPA-20, 2003 NFPA-101, 2002
 NFPA-110.
 IT IS KNOW THAT THIS PROJECT CAME IN UNDER THE 2001
 FBC.
  
 3) NOTE: PLEASE SUBMIT ALL THE MANUFACTURE SPECS/CUT
 SHEETS FOR ALL OF THE FOLLOWING. PLEASE SUBMIT FOR;
 FIRE PUMP, FIRE PUMP CONTROLLER, GENERATOR, FUEL TANK.
 (SEENOTES BELOW), ATS EQUIPMENT (SEENOTESBELOW).
 110.3, 90.7
  
  
 4) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS. (ALL CORRIDORS AND STAIR TOWERS) PLEASE
 SEE LS-1017.8.1.3, 7.9.2.2 10FT CANDLE MIN FOR STAIRS
 UNDER NORMAL AND 1FT CANDLE UNDER EM.
  
 ** PLEASE ALSO BE AWARE OF ZONING COMMENTS AS
 PHOTO-METRICS WILL ALSO BE REQUIRED FOR FUTURE PARKING
 GARAGE.
  
 5) NOTE: PLEASE SEE ZONING COMMENTS, PLEASE SEE IF A
 GARAGE IS NOW REQUIRED, THIS WILL COMPLETELY CHANGE
 ELECTRICAL SERVICE AND ELECTRICAL SHEETS SUBMITTED.
  
 6) NOTE: PLEASE SEE PREVIOUS PLANS WHICH WERE RED-LINED
 FOR CIRCUITING OF ELEVATOR MACHINE ROOMS PER 620.23,
 620.24 AND ASSOCIATED EQUIPMENT. THIS HAS NOT BEEN
 CORRECTED ON PLANS TO DATE.
  
 7) NOTE: PLEASE SEE ALL FIXTURE SCHEDULE AND TYPE
 INFORMATION WHICH WAS ON PREVIOUS PLANS HAS BEEN
 REMOVED FOR EM FIXTURES?
 PLEASE SEE ALL OF THE FOLLOWING IN ORDER TO REVIEW FOR
 CODE COMPLIANCE SHALL BE PLACED BACK ON PLANS.
 LS 101
  
 8) NOTE: PLEASE SEE THAT NOW THAT A GENERATOR IS
 INSTALLED AND REQUIRED AND USE IS TO A HIGH-RISE,
 PLEASE SEE NFPA-20 6-6.2 AS THE MINIMUM FUEL REQUIRED
 FOR FIRE PUMP IS 8HRS AT 100%, AND 5% FOR EXPANSION AND
 5% FOR SUMP.
 PLEASE SEE TANK AS SHOWN AND FUEL CALCULATIONS CAN NOT
 VERIFIED AS NO INFORMATION WAS SUBMITTED.
  
 9) NOTE: PLEASE SEE NFPA-20 CHAPTER 6 AND 7 FOR FIRE
 PUMP, ASTHERE ARE TOO MANY SECTIONS TO BE LISTED FOR
 ITEMS NEEDED FOR REVIEW.
  
 10) NOTE: PLEASE SEE NFPA-110 CHAPTER 7,7.2.3 FOR MIN
 ELEVATION REQUIRED FOR ALL EPSS EQUIPMENT INCLUDING
 GEN.
 PLEASE PROVIDE MIN LEVELS FOR "SLOSH" ( SEA, LAKE,
 OVERLAND , SURGES, BY HURRICANES) CHARTS BASED ON A CAT
 4 STORM OR THE 100YR ELEVATION ON PLANS.
  
 11) NOTE: PLEASE SEE POOL AREA PHOTO-METRICS ARE TO BE
 REVIEWED AND STAMPED BY THE PALM BEACH COUNTY HEALTH
 DEPARTMENT IF ANY SWIMMING WILL TAKE PLACE OR PERMITTED
 FROM DUSK TO DAWN. PLEASE KNOW THAT THE POOL WILL ALSO
 BE REQUIRED UNDER A SEPARATE PERMIT.
 IF NO SWIMMING , PLEASE PROVIDE NOTES ON THESE PLANS AT
 THIS TIOME, EVEN THOUGH THE POOL WILL BE UNDER A
 SEPARATE PERMIT.
  
 12) NOTE: PLEASE SEE SOME SHEETS ARE MISSING TITLE
 BLOCK INFORMATION AS REQUIRED FOR ENGINEER. PLEASE SEE
 MISSING THE PRINTED NAME, PRINTED LICENSE # AND MISSING
 THE DATE WHEN PLANS WERE SIGNED AND SEALED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
  
 13) NOTE: PLEASE CORRELATE AND LABEL ALL MAINS ON
 SCHEDULES, RISER AND MAIN ELECTRICAL ROOM(S). PLEASE
 SEE SCHEDULES DO NOT CORRELATE WITH RISER, ETC. 230.2E
 ETC,
  
 14) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL
 EQUIPMENT, ATS, DISCONNECTS ETC. PLEASE SEE 701.6,
 NFPA-20 6-3.2.2.4, 110.9, 240.12 ETC. PLEASE SEE
 NFPA-110 6.5.2 ETC.
 PLEASE BE SURE ALL EQUIPMENT/MANUFACTURE SPECS/CUT
 SHEETS SHOWS THIS COORDINATION.
  
 15) NOTE: PLEASE SEE NEC 11.26 FOR MAXIMUM DISTANCE A
 GUTTER OR ANY OTHER EQUIPMENT SHALL PROTRUDE IN FRONT
 OF EQUIPMENT. (6") PLEASE SEE RISER AND PROVIDE A SIDE
 ELEVATION TO INDICATE IF EQUIPMENT WILL BE MOUNTED OUT
 FROM THE WALL.
 PLEASE ALSO SEE THE FOLLOWING COMMENT FOR SIZING GUTTER
 TO MAIN 2 AND 3 ON RISER. (SHOWN AS DIFFERENT MAINS ON
 OTHER SECTIONS OF PLANS SEE NOTE #13).
  
 16) NOTE: PLEASE SEE 240.4C, AS THE SEC'S FROM FPL TO
 GUTTER SHALL BE RATED AT 1200A?S OR ABOVE.
 90.4.
  
 17) NOTE: PLEASE ALSO VERIFY THE SIZE OF THE GUTTER FOR
 MAINS #2 AND #3 ON RISER. PLEASE SEE 366.
  
 18) NOTE: PLEASE SEE MISSING A DISCONNECTING MEANS
 REQUIRED FOR THE FEEDERS COMING FROM THE GENERATOR TO
 MEET 701.11(B)5.
  
 19) NOTE: PLEASE PROVIDE DETAIL FOR VERTICAL CONDUCTOR
 SUPPORTS PER 300.19(A).
  
 20) NOTE: PLEASE SEE NFPA-110 FOR ATS EPSS EQUIPMENT
 SECTION: 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED
 TO BE INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM
 WHERE TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A)
 OF NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
 THIS DOES NOT APPEAR TO BE MET AT THIS TIME.
  
 21) NOTE: PLEASE PROVIDE ALL MINIMUM AUDIBLE AND VISUAL
 LEVELS PER FBC 2001 11-4.28, 11-4.28.2 AND MOST
 IMPORTANT 11-4.28.3(4). ALL AREA AS STATED IN 11-4.28.1
 SHALL BE NOTED AND INLCUDED. THIS COMMENT WAS NEVER
 UNDER ELECTRICAL REVIEW SCOPE ON PREVIOUS REVIEWS UNTIL
 RECENTLY.
  
 22) NOTE: PLEASE INCLUDE A NOTE ON ROOF TOP PLANS WHICH
 WILL STATE THAT "ANY LIGHTNING PROTECTION SYSTEM TO BE
 INSTALLED SHALL MEET NFPA-780" OR WORDS TO THAT AFFECT.
 A SYSTEM IS NOT REQUIRED, HOWEVER THE NOTE IS,AS THERE
 ARE MANY SYSTEMS BEING "PROMOTED AND SOLD" IN THE STATE
 OF FLORIDA WHICH ARE STRICTLY NOT PERMITTEDAND MANY
 KNOWN SYSTEMS ARE ACTUALLY A HEALTH AND LIFE SAFETY
 HAZARD. PLEASE SEE ONLY IF IN NFPA-780.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED. PLEASE KNOW THERE MAY BE FUTURE COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2006-10-29 06:55:15REVIEW IN PROGRESS
2006-10-28 19:23:25ONE ROLL IN ELECTRICAL FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved