| 2006-08-20 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | SITE PLAN (SHEET A-101) AND FOUNDATION |
| | PLAN (SHEET S-1) AND DETAIL SHEET (SHEET |
| | S-2) REVISION FOR ADDITION OF THREE |
| | STORIES (6TH, 7TH AND 8TH FLOORS) TO THE |
| | BUILDING. |
| | |
| | 1) FBC* 104.6THE DECLARED BUILDING |
| | VALUE SHALL BE INCREASED TO ACCOUNT FOR |
| | THE THREE ADDITIONAL STORIES AND THE |
| | STRENGTHENING OF THE |
| | STRUCTURE/FOUNDATION TO SUPPORT THEM. |
| | THE PERMIT FEES WILL THEN BE ADJUSTED |
| | ACCORDINGLY. |
| | |
| | 2) IMPACT FEES AND RADON FEES.PLEASE |
| | NOTE THAT ADDITIONAL IMPACT FEES AND |
| | RADON FEES WILL BE DUE FOR THE INCREASE |
| | IN BUILDING AREA. |
| | |
| | 3) FBC 11-4.1.2(5) AND 11-4.6.5SHEET |
| | A-101, REVISED PARKING TABLE.ANNOTATE |
| | THE PLAN TO CLARFIY HOW THE PROPOSED |
| | PARKING STRUCTURE WILL BE USED.IS THE |
| | PARKING STRUCTURE FOR USE BY VALET ONLY? |
| | IF SO, THEN AN ACCESSIBLE PASSENGER |
| | LOADING ZONE COMPLYING WITH FBC 11-4.6.6 |
| | LOCATED ON AN ACCESSIBLE ROUTE TO THE |
| | BUILDING ENTRANCE IS REQUIRED. |
| | IF THE PARKING STRUCTURE IS NOT FOR USE |
| | BY VALET ONLY, PLEASE NOTE THAT EIGHT OF |
| | THE PROPOSED 146 PARKING SPACES ARE |
| | SHOWN AS UNCOVERED.SO IT IS ASSUMED |
| | THAT THE PARKING STRUCTURE WILL PROVIDE |
| | THE REMAINING SPACES AS COVERED PARKING. |
| | IN THAT CASE, A PORTION OF THE |
| | ACCESSIBLE PARKING SPACES SHALL BE IN |
| | THE PARKING STRUCTURE TO PROVIDE COVERED |
| | PARKING FOR HANDICAPPED PERSONS.ALSO, |
| | ONE IN EIGHT (NOT LESS THAN ONE) OF THE |
| | SPACES IN THE PARKING STRUCTURE SHALL BE |
| | VAN ACCESSIBLE COMPLYING WITH FBC |
| | 11-4.6.5. ANNOTATE THE PLAN TO CLARFIY |
| | HOW THE PROPOSED PARKING STRUCTURE WILL |
| | BE USED. |
| | |
| | 4)FOUNDATION TYPE.THE PLANS |
| | PREVIOUSLY SHOWED CONCRETE FOOTINGS FOR |
| | COLUMNS AND WALLS AND A 4" CONCRETE |
| | FIRST FLOOR SLAB.THE REVISED SHEET S-1 |
| | NOW INCLUDES A NOTE CALLING OUT A 30" |
| | THICK CONCRETE MAT FOUNDATION BUT IT |
| | ALSO STILL SHOWS A NOTE CALLING OUT A 4" |
| | CONCRETE SLAB. WHAT IS THE FOUNDATION |
| | FOR COLUMNS TC-3, TC-6, TC-7 ETC AND FOR |
| | THE SPIRAL STAIRS.ANNOTATE THE PLAN |
| | AND PROVIDE CROSS SECTION DETAILS TO |
| | CLARIFY THE EXTENT OF THE MAT FOUNDATION |
| | AND THEPROPOSED FOUNDATION AND SLAB |
| | ARRANGEMENT. |
| | |
| | 5) FBC* 104.2.1SHEET S-2 WAS |
| | PREVIOUSLY THE MEZZANINE FRAMING PLAN. |
| | THE DETAILS SHOWN ON THE REVISED SHEET |
| | S-2 WERE PREVIOUSLY SHOWN ON SHEET S-9. |
| | IS THAT INTENTIONAL?PLEASE NOTE THAT |
| | THE NEW VERSION OF S-2 (STRUCTURAL |
| | DETAILS) WILL REPLACE THE PREVIOUS S-2 |
| | (MEZZANINE FRAMING PLAN) SUCH THAT THERE |
| | IS NO LONGER A MEZZANINE FRAMING PLAN. |
| | PLEASE CORRECT OR CLARIFY. |
| | |
| | 6) FBC* 104.2.1SHEETS S-1 AND S-2. |
| | WHEN SUBMITTING REVISED PLANS, PLEASE |
| | USE REVISION MARKERS (AND 'CLOUDS') TO |
| | CLEARLY SHOW WHAT AREAS HAVE BEEN |
| | REVISED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652ROBERT BROWN |
| | E-MAIL: [email protected] |
| | |