Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop P
Sequence Number 2
Notes
Date Text
2005-08-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW:
  
 1. CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHEET P-6
 INDICATES SIZE OF SECONDARY ROOF DRAINS
 REQUIRED AS 18 SQ. IN., BUT MINIMUM 22
 SQ. IN. REQUIRED PER SECTION 1107 AND
 TABLE 1106.3 IN MOST SECTIONS. A MINIMUM
 OF 36 SQ.IN. IS REQUIRED IN SECTIONS 6
 AND 7. - PLEASE RECHECK ALL AREAS AS
 SOME AREAS SHOW NO VERTICAL AREAS OR
 UPPER ROOF AREAS AND THEY ARE NEXT TO
 PARAPET WALLS, BELVEDERE WALLS & ROOFS,
 SPA EQUIPMENT OR RESTROOM WALLS,
 STAIRWAY WALLS ECT. SHOW ALL WALLS AND
 ROOF AREAS THAT DRAIN ONTO ROOFS IN
 CALCULATIONS. (SEE CALCULATIONS ATTACHED
 FOR AREAS 1 & 2) - SCUPPER SIZES
 INDICATED ON SHT P-6 CALCULATIONS STATE
 6"X1.5". THE BUILDING ELEVATIONS
 INDICATE THAT THE SCUPPERS WILL BE
 CYLINDRICAL AND IF SO PLEASE INDICATE
 WHAT THE 1.5" MEASUREMENT IS REFERING
 TO.
 8. SHT P-12 WATER HEATER DETAIL. NO T&P
 LINES SHOWN ON THE WATER HEATERS.
 SECTION 504.5 - BOTTOM FED WATER HEATERS
 AND STORAGE TANK SHALL HAVE A VACUUM
 RELIEF VALVE INSTALLED AT THE HIGHEST
 POINT OF THE WATER INLET. SECTION 504.2
 WATER HEATERS SHALL BE PIPED ACCORDING
 TO MANUFACTURES INSTALLATION
 INSTRUCTIONS. SECTION 502.1.
  
 REVIEW BY KEN STEVENS