Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop FUEL
Sequence Number 2
Notes
Date Text
2008-05-27 11:17:46SEE PREVIOUS REVIEW COMMENTS DATED 3/4/08. NONE OF THE
 REQUESTED INFORMATION COULD BE FOUND ON THE PLANS
 REGARDING THE SIZE OF THE TANK, VENTING OF THE TANK,
 VENTILATION AND EXHAUST FOR THE GENERATOR. PLEASE
 PROVIDE ALL RELEVANT INFORMATION SHOWING ALL COMPONENTS
 OF THE GENERATOR INSTALLATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719