2005-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) SHTS A-108, A-109, & P-6 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS. SHOW TOTAL SQUARE
 FOOTAGE FOR EACH AREA BEING DRAINED.
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS, AND AREAS OF ROOF
 THAT DRAIN ONTO THE DIFFERENT AREAS
 ADDED TO ROOF AREA IN CALCULATIONS. SHOW
 THE LOCATION OF ALL SECONDARY ROOF
 DRAINS INCLUDING AREAS THAT ARE NOT
 ADJACENT TO THE OUTER WALLS.
 2) SHTS A-103 & P-2. SHT A-103 SHOWS A
 STORAGE ROOM, BUT P-2 SHOWS A LAUNDRY -
 WATER HEATER ROOM. PLEASE CLARIFY.
 SECTION 104.2.1.
 3) SHTS P-1 & P-2. SHT P-1 SHOWS SANT.
 RISER #11 UP TO MEZZ. LEVEL, BUT DOES NT
 SHOW UP ON P-2. PLEASE CORRELATE PLANS.
 SECTION 104.2.1.
 4) SHT P-6 AREAS AROUND THE ENDS OF THE
 SPA, WHERE THE SPA HAS BEE REDUCED IN
 SIZE, SHALL BE INCREASED TO REFLECT THE
 LARGER AREAS TO BE DRAINED. SECTION
 104.2.1.
 5) SHT P-7 SHOWS WATER PIPING TO GROUND
 FLOOR LAUNDRY, BUT THIS HAS BEEN DELETED
 ON THE FLOOR PLAN. PLEASE DELETE WATER
 DETAIL FOR GROUND FLOOR LAUNDRY. SECTION
 104.2.1.
 6) SHT P-7 SANITARY RISER S/8 AND BRANCH
 LINE TO RISER ARE NOT SHOWN ON THE BLDG.
 DRAIN ISOMETRIC. SECTION 104.2.1.
 8) SHT P-12 WATER HEATER DETAIL. T&P
 RELIEF VALVE DISCHARGE LINES SHOW VALVES
  
 AND ARE TIED TOGETHER AND VALVED PRIOR
 TO ENTERING THE STORAGE TANK. THIS IS
 NOT APPROVED PER SECTIONS 504.5.1 AND
 504.7.1. - ALSO THE STORAGE TANK SHOWS
 NO DISCHARGE PIPING. SHOW THE
 TERMINATION POINT FOR RELIEF VALVES.-
 BOTTOM FED WATER HEATERS AND STORAGE
 TANKS SHALL HAVE A VACUUM RELIEF VALVE
 INSTALLED. SECTION 504.2.-WATER
 HEATER SHOW NO HOT WATER LINES EXITING
 THE HEATERS. - WATER HEATERS SHALL BE
 PIPED IN SUCH AN ARRANGEMENT TO SUPPLY
 AND DISCHARGE SIMULTANEOUSLY FROM EACH
 WATER HEATER.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  