2005-05-26 00:00:00DENIED:
 1.PLAN SHEET AC-1 INDICATES RETURN AIR
 PLENUM PENETRATING THE FLOOR TO AHU-1
 AND DOES NOT INDICATE A FIRE DAMPER.
 PER 2001 FBC/M 607.4, DUCTS PENTRATING
 ONLY ONE FLOOR CAN BE PROTECTED BY A
 FIRE DAMPER IN LIEU OF A SHAFT.
  
 2.PLAN SHEET AC-1, PLEASE CLARIFY
 TERMINATION OF EF-3.IT APPEARS TO
 TERMINTE AT STAIRWAY, PER 2001 FBC/M
 401.5.2, EXHAUST OPENINGS SHALL
 TERMINATE AS NOT TO CREATE A NUISANCE
 AND SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 3.THE PLANS INDICATE FUTURE RESTAURANT
 PLAS INDICATE THE TERMINATION OF GREASE
 DUCT ON THE ROOF.PLEASE NOTE GREASE
 DUCT SHALL BE ENCLOSED IN A 2 HR RATED
 SHAFT.
  
 4.PLANS INDICATE CORRIDORS BEING
 UTILIZED AS PLENUMS OR TRANSFERS.PER
 2001 FBC/M 601.2, EXITS & EXIT ACCESS
 CORRIDORS SHALL NOT BE SERVE AS RETURN,
 EXHAUST RELIEF OR VENTILATION AIR DUCTS
 OR PLENUMS.
  