| Plan Review Notes For Permit 05031185 |
| Permit Number |
05031185 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-26 00:00:00 | DENIED: | | | 1.PLAN SHEET AC-1 INDICATES RETURN AIR | | | PLENUM PENETRATING THE FLOOR TO AHU-1 | | | AND DOES NOT INDICATE A FIRE DAMPER. | | | PER 2001 FBC/M 607.4, DUCTS PENTRATING | | | ONLY ONE FLOOR CAN BE PROTECTED BY A | | | FIRE DAMPER IN LIEU OF A SHAFT. | | | | | | 2.PLAN SHEET AC-1, PLEASE CLARIFY | | | TERMINATION OF EF-3.IT APPEARS TO | | | TERMINTE AT STAIRWAY, PER 2001 FBC/M | | | 401.5.2, EXHAUST OPENINGS SHALL | | | TERMINATE AS NOT TO CREATE A NUISANCE | | | AND SHALL NOT BE DIRECTED ONTO WALKWAYS. | | | | | | 3.THE PLANS INDICATE FUTURE RESTAURANT | | | PLAS INDICATE THE TERMINATION OF GREASE | | | DUCT ON THE ROOF.PLEASE NOTE GREASE | | | DUCT SHALL BE ENCLOSED IN A 2 HR RATED | | | SHAFT. | | | | | | 4.PLANS INDICATE CORRIDORS BEING | | | UTILIZED AS PLENUMS OR TRANSFERS.PER | | | 2001 FBC/M 601.2, EXITS & EXIT ACCESS | | | CORRIDORS SHALL NOT BE SERVE AS RETURN, | | | EXHAUST RELIEF OR VENTILATION AIR DUCTS | | | OR PLENUMS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|