| 2005-04-21 00:00:00 | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS. | | | | | | 2) LOCK CAPS ARE REQUIRED ON FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | 3) FDC LOCATIONS ARE DIFFERENT ON SHEETS | | | SFP-1 AND FP-1. PLEASE INDICATE THE | | | LOCATIONS. | | | | | | 4) PLEASE INDICATE THE PRESCRIPTIVE CODE | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GUARDRAILS. | | | | | | 5) PLANS DON'T SHOW ANY AUTOMATIC FIRE | | | DETECTION DEVICES IN THE ELEVATOR | | | HOISTWAYS. | | | | | | 6) EMERGENCY LIGHTING IS REQUIRED IN THE | | | FIRE PUMP ROOM. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|