Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-19 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE E-1 ELECTRICAL ROOM
 LAYOUT WHICH DOES NOT INLCUDE ANY
 ELECTRICAL EQUIPMENT ,HOWEVER THIS ROOM
 SHOWS A NEW EF-7?
 PLEASE CORRELATE WITH "BLOW-UP" OF
 ELECTRICAL RM ON E-7
  
 2)NOTE: PLEASE SEE MAINS FOR ELEVATOR'S
 SHALL BE LABELED MAIN 4 OF 5 AND 5 OF 5.
 230.70,71 ETC.
  
 3)NOTE: PLEASE SEE 620.23 ETC FOR
 CIRCUITING.
  
 4)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS INSTALLED FROM
 FPL TO FIRST MEANS OF DISCONNECT FOR
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE 250.6,250.24, EQUIPMENT
 GROUNDING IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 PLEASE KNOW, IF PLANS DO NOT COME BACK
 WITH ANY COMMENTS FROM ANY OF THE OTHER
 REVIEWER(S) THIS MAY BE DONE AS A
 PROVISO FOR NEW REVISED SHEETS TO BE
 PROVIDED BEFORE ANY SLAB INSPECTION.
  
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2005-04-18 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.