| 2005-04-19 00:00:00 | ***** UNSAT ****** |
| | |
| | 1)NOTE: PLEASE SEE E-1 ELECTRICAL ROOM |
| | LAYOUT WHICH DOES NOT INLCUDE ANY |
| | ELECTRICAL EQUIPMENT ,HOWEVER THIS ROOM |
| | SHOWS A NEW EF-7? |
| | PLEASE CORRELATE WITH "BLOW-UP" OF |
| | ELECTRICAL RM ON E-7 |
| | |
| | 2)NOTE: PLEASE SEE MAINS FOR ELEVATOR'S |
| | SHALL BE LABELED MAIN 4 OF 5 AND 5 OF 5. |
| | 230.70,71 ETC. |
| | |
| | 3)NOTE: PLEASE SEE 620.23 ETC FOR |
| | CIRCUITING. |
| | |
| | 4)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS INSTALLED FROM |
| | FPL TO FIRST MEANS OF DISCONNECT FOR |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE SEE 250.6,250.24, EQUIPMENT |
| | GROUNDING IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | PLEASE KNOW, IF PLANS DO NOT COME BACK |
| | WITH ANY COMMENTS FROM ANY OF THE OTHER |
| | REVIEWER(S) THIS MAY BE DONE AS A |
| | PROVISO FOR NEW REVISED SHEETS TO BE |
| | PROVIDED BEFORE ANY SLAB INSPECTION. |
| | |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO THREE COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |