Plan Review Notes
Plan Review Notes For Permit 05031185
Permit Number 05031185
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-31 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC* 105.13.1SPECIAL INSPECTOR
 AGREEMENT.THE SUBMITTED AGREEMENT
 LISTS THE WEITZ COMPANY AS CONTRACTOR
 (SHOULD BE J RAYMOND CONSTRUCTION CORP),
 HAS NO ORIGINAL SIGNATURES OR RAISED
 SEALS AND REFERS TO THE OLD PERMIT#
 03121642.SUBMIT THREE (3) COPIES OF A
 NEW SPECIAL INSPECTOR AGREEMENT.THE
 AGREEMENT SHALL INCLUDE THE NEW PERMIT
 NUMBER (05031185) AND SHALL BE SIGNED BY
 AN AUTHORIZED SIGNATORY FOR J. RAYMOND
 CONSTRUCTION CORP.ORIGINAL SIGNATURES
 ARE REQUIRED (WITH RAISED SEALS FOR
 ENGINEERS/ARCHITECTS)
  
 4) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ALSO, THE SIGNATURE OF RAFAEL PENA IS A
 COPY.AN ORIGINAL SIGNATURE IS
 REQUIRED.
  
 5) FBC 2803PACKAGED TERMINAL AIR
 CONDITIONER (PTAC), SECTIONS A-401/1 TO
 A-402/4 AND S-11/1 TO S-11/3.SUBMIT
 DETAILS TO SHOW HOW THE PTAC AND
 ALUMINUM LOUVER WILL PREVENT WIND-DRIVEN
 RAIN FROM ENTERING THE BUILDING.
  
 6) FBC* 2111.1.9WATER STOP, DETAIL
 A-503/4 AND SECTIONS A-301 TO A-402 AND
 S-11/1 TO S-11/2.THE REQUIRED 1.5"
 SLAB RECESS IS NOT SHOWN.AMEND THE
 PLANS OR MAKE A PROPOSAL, FOR
 CONSIDERATION UNDER FBC* 103.7 ALTERNATE
 MATERIALS AND METHODS, FOR
 WATER-PROOFING THE 'COLD JOINT' BETWEEN
 WALL AND SLAB.
  
 7) FBC 707.1 CONCEALED SPACES IN TYPE II
 CONSTRUCTION.SHEETS A-503 AND A-502
 DETAIL 11, SHOW WOOD BLOCKING.ALL
 BUCKS, HEADERS, BLOCKING AND FIRRING
 STRIPS ETC SHALL BE FIRE RETARDANT
 TREATED LUMBER IN TYPE I, II AND IV
 CONSTRUCTION.AMEND/ANNOTATE THE PLANS.
  
 8) FBC 1606.1TRUSS ANCHOR SCHEDULE,
 SHEET S-9 AND SHEET S-11 SECTION 2.A
 COMBINED CAPACITY FOR TWO (2) SIMPSON
 META 22 OF 2900# IS STATED ON THE
 SCHEDULE.THIS EXCEEDS THE MAX. (TWO
 ANCHOR) COMBINED UPLIFT OF 2565# ALLOWED
 IN THE 2005 SIMPSON CATALOGUE.AMEND
 THE SCHEDULE.
  
 9) THE SUBMITTED GAF BUILT-UP ROOFING
 PRODUCT APPROVAL (STATEWIDE# FL618 AND
 MIAMI-DADE NOA# 00-0403.02) COVERS
 SYSTEMS WITH DESIGN PRESSURE RATINGS
 THAT RANGE FROM -45 PSF TO 457.5 PSF, SO
 SOME OF THE SYSTEMS ARE NOT SUITABLE FOR
 THIS PROJECT.MARK THE NOA TO SHOW
 WHICH SYSTEM IS PROPOSED SO THAT THAT
 THE DESIGN PRESSURE CAN BE COMPARED WITH
 THE CALCULATED PRESSURES FOR THE
 BUILDING.
  
 10) FBC 1606.1.4IMPACT RATING OF
 SINGLE HUNG WINDOWS.THE SUBMITTED PGT
 SINGLE HUNG WINDOW STATEWIDE PRODUCT
 APPROVAL FL239 COVERS NON-IMPACT, SMALL
 MISSILE IMPACT AND LARGE MISSILE IMPACT.
 THE MIAMI-DADE PRODUCT APPROVAL (NOA#
 02-0123.04) THAT WAS SUBMITTED, IS FOR
 SMALL MISSILE IMPACT RATED WINDOWS, SO
 IT IS NOT APPLICABLE FOR THE WINDOWS
 BELOW 30 FEET ABOVE GRADE.SUBMIT THREE
 COPIES OF A PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT RATED WINDOWS.
  
 11) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]