| 2005-05-31 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | |
| | 1) 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 105.13.1SPECIAL INSPECTOR |
| | AGREEMENT.THE SUBMITTED AGREEMENT |
| | LISTS THE WEITZ COMPANY AS CONTRACTOR |
| | (SHOULD BE J RAYMOND CONSTRUCTION CORP), |
| | HAS NO ORIGINAL SIGNATURES OR RAISED |
| | SEALS AND REFERS TO THE OLD PERMIT# |
| | 03121642.SUBMIT THREE (3) COPIES OF A |
| | NEW SPECIAL INSPECTOR AGREEMENT.THE |
| | AGREEMENT SHALL INCLUDE THE NEW PERMIT |
| | NUMBER (05031185) AND SHALL BE SIGNED BY |
| | AN AUTHORIZED SIGNATORY FOR J. RAYMOND |
| | CONSTRUCTION CORP.ORIGINAL SIGNATURES |
| | ARE REQUIRED (WITH RAISED SEALS FOR |
| | ENGINEERS/ARCHITECTS) |
| | |
| | 4) FBC 13-103.1.2BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | ALSO, THE SIGNATURE OF RAFAEL PENA IS A |
| | COPY.AN ORIGINAL SIGNATURE IS |
| | REQUIRED. |
| | |
| | 5) FBC 2803PACKAGED TERMINAL AIR |
| | CONDITIONER (PTAC), SECTIONS A-401/1 TO |
| | A-402/4 AND S-11/1 TO S-11/3.SUBMIT |
| | DETAILS TO SHOW HOW THE PTAC AND |
| | ALUMINUM LOUVER WILL PREVENT WIND-DRIVEN |
| | RAIN FROM ENTERING THE BUILDING. |
| | |
| | 6) FBC* 2111.1.9WATER STOP, DETAIL |
| | A-503/4 AND SECTIONS A-301 TO A-402 AND |
| | S-11/1 TO S-11/2.THE REQUIRED 1.5" |
| | SLAB RECESS IS NOT SHOWN.AMEND THE |
| | PLANS OR MAKE A PROPOSAL, FOR |
| | CONSIDERATION UNDER FBC* 103.7 ALTERNATE |
| | MATERIALS AND METHODS, FOR |
| | WATER-PROOFING THE 'COLD JOINT' BETWEEN |
| | WALL AND SLAB. |
| | |
| | 7) FBC 707.1 CONCEALED SPACES IN TYPE II |
| | CONSTRUCTION.SHEETS A-503 AND A-502 |
| | DETAIL 11, SHOW WOOD BLOCKING.ALL |
| | BUCKS, HEADERS, BLOCKING AND FIRRING |
| | STRIPS ETC SHALL BE FIRE RETARDANT |
| | TREATED LUMBER IN TYPE I, II AND IV |
| | CONSTRUCTION.AMEND/ANNOTATE THE PLANS. |
| | |
| | 8) FBC 1606.1TRUSS ANCHOR SCHEDULE, |
| | SHEET S-9 AND SHEET S-11 SECTION 2.A |
| | COMBINED CAPACITY FOR TWO (2) SIMPSON |
| | META 22 OF 2900# IS STATED ON THE |
| | SCHEDULE.THIS EXCEEDS THE MAX. (TWO |
| | ANCHOR) COMBINED UPLIFT OF 2565# ALLOWED |
| | IN THE 2005 SIMPSON CATALOGUE.AMEND |
| | THE SCHEDULE. |
| | |
| | 9) THE SUBMITTED GAF BUILT-UP ROOFING |
| | PRODUCT APPROVAL (STATEWIDE# FL618 AND |
| | MIAMI-DADE NOA# 00-0403.02) COVERS |
| | SYSTEMS WITH DESIGN PRESSURE RATINGS |
| | THAT RANGE FROM -45 PSF TO 457.5 PSF, SO |
| | SOME OF THE SYSTEMS ARE NOT SUITABLE FOR |
| | THIS PROJECT.MARK THE NOA TO SHOW |
| | WHICH SYSTEM IS PROPOSED SO THAT THAT |
| | THE DESIGN PRESSURE CAN BE COMPARED WITH |
| | THE CALCULATED PRESSURES FOR THE |
| | BUILDING. |
| | |
| | 10) FBC 1606.1.4IMPACT RATING OF |
| | SINGLE HUNG WINDOWS.THE SUBMITTED PGT |
| | SINGLE HUNG WINDOW STATEWIDE PRODUCT |
| | APPROVAL FL239 COVERS NON-IMPACT, SMALL |
| | MISSILE IMPACT AND LARGE MISSILE IMPACT. |
| | THE MIAMI-DADE PRODUCT APPROVAL (NOA# |
| | 02-0123.04) THAT WAS SUBMITTED, IS FOR |
| | SMALL MISSILE IMPACT RATED WINDOWS, SO |
| | IT IS NOT APPLICABLE FOR THE WINDOWS |
| | BELOW 30 FEET ABOVE GRADE.SUBMIT THREE |
| | COPIES OF A PRODUCT APPROVAL FOR LARGE |
| | MISSILE IMPACT RATED WINDOWS. |
| | |
| | 11) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |