| Plan Review Notes For Permit 05031177 |
| Permit Number |
05031177 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 3.1 LUNCH ROOM SINK SHALL COMPLY | | | WITH 11-4.24 AND ALL SUBSECTIONS. SHOW: | | | A) HEIGHT 11-4.24.2 | | | B) KNEE CLEARANCE 11-4.24.3 | | | C) SINK DEPTH 11-4.24.4 | | | D) CLEAR FLOOR SPACE 11-4.24.5 FORWARD | | | APPROACH REQUIRED. MAXIMUM 19" | | | UNDERNEATH THE SINK. NO CABINET DOORS | | | ALLOWED. | | | E) EXPOSED PIPES & SURFACES 11-4.24.6 | | | F) FAUCETS 11-4.24.7 | | | 2) A DRINKING FAUCET IS REQUIRED PER | | | TABLE 403.1. | | | 3) SHT M1 WATER ISOMETRIC. FULL OPEN | | | VALVES ARE REQUIRED ON ALL WATER | | | DOWN-FEED LINES. SECTION 606.1(4). | | | 4) SHT M1 PLUMBING NOTES #10, AIR | | | CHAMBERS ARE NOT APPROVED. SECTION 604.9 | | | IF WATER HAMMER ARRESTORS ARE PROVIDED, | | | THEY SHALL BE LOCATED NEAR THE FIXTURE | | | IN AN "EFFECTIVE RANGE" NOT IN THE | | | CEILING. PDI-WH 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|