| 2005-03-25 00:00:00 | ******* UNSAT ****** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER/ PANEL |
| | SCHEDULE/ PLANS. |
| | RISER DOES NOT INDICATE APANEL "A", |
| | HOWEVER SHOWS A PANEL "B"?? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE PLANS INDICATE AN |
| | EXSITING COND UNIT, HOWEVER PANEL |
| | SCHEDULE INDICATES A NEW COND UNIT? |
| | |
| | 3)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | GFI REQUIRED FOR COND UNITS. 210.63 |
| | PANEL SCHEDULE INDICATES AND EXSITNG |
| | ROOFTOP RECEPT. |
| | |
| | 4)NOTE: PLEASE SHOW ALL DISC'S REQUIRED |
| | FOR AHU'S , CU'S. 440.11 |
| | |
| | 5)NOTE: PLEASE SEE MISSING "SHOW WINDOW" |
| | RECEPTS ON PLANS. PANEL SCHEDULE |
| | INDICATES "SHOW WINDOW" RECEPTS, HOWEVER |
| | THESE CIRCUITS ARE SHOWN GOING TO A |
| | POWER POLE LOCATED IN THE CENTER OF THE |
| | SHOWROOM. |
| | PLEASE SEE 210.62, 220.12, NO OTHER |
| | LOADS ARE PERMITTED ON SHOW WINDOW |
| | CIRCUIT, PLEASE ALSO SEE 200 VA PER FT. |
| | |
| | 6)NOTE: PLEASE VERIFY #3 EQUIPMENT |
| | GROUNDING CONDUCTOR SHOWN FROM 175A MAIN |
| | BRKR TO PANEL. THIS IS PERMITTED AND |
| | ONLY A NOTE: |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | THIS WILL HELP IN PROCESS TO EXPEDITE |
| | PLANS FOR PERMITTING. |
| | PLEASE SUBMIT ONE COPY OF ANY OLD SHEETS |
| | FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESTITATE TO CALL. |
| | |