| Plan Review Notes For Permit 05031157 |
| Permit Number |
05031157 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) MORE INFORMATION FOR ROOF DRAINAGE IS | | | REQUIRED. SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | THE SQUARE FOOTAGE OF THE ROOF AND SHOW | | | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING | | | PARAPETS. INDICAT SQUARE FOOTAGE TO BE | | | DRAINING INTO THE PRIMARY ROOF DRAIN. | | | ONLY ONE ROOF DRAIN SHOWN. SHOW THE SIZE | | | OF THE NEW OVERFLOW SCUPPER AND | | | DOWNSPOUT. SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS AND TABLES. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|