| Plan Review Notes For Permit 05031157 |
| Permit Number |
05031157 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-18 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05031157 | | | ADD: 500 PALM STREET STE"C" | | | CONT:MIKE MOORE CONST | | | TEL: (561)262-0314 | | | | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PLANS INDICATE ROOF DAMAGE TO THE | | | MANSARD ROOFING, NO PRODUCT INFORMATION | | | WAS PROVIDED FOR THE METAL ROOF.NOTE | | | THIS IS IN THE FIRE DISTRICT A CLASS A | | | OR B ROOF COVERING IS REQUIRED F102.2.4. | | | | | | 2) THE BUILT UP ROOFING PRODUCT APPROVAL | | | SUBMITTED DOESN'T INDICATE WHICH SYSTEM | | | IS TO BE USED. THE SECOND ISSUE IS LOW | | | PRESSURES FOR ZONE THREE.PLANS INDICATE | | | -68.2 IN ZONE THREE. | | | | | | 3) THE PLANS INDICATE WOOD ROOF FRAMING | | | BUT NO INDICATION IF THIS IS NEW WORK OR | | | EXISTING? WHAT TYPE OF SPECIES OF WOOD | | | IS USED AND THE GRADE TO DETERMINE THE | | | SPANS? PROVIDE LIVE LOAD/ DEAD LOADS AND | | | | | | DEFLECTION LIMITATION. FL BLD CODE | | | 104.2.1.2 ADDITIONAL INFORMATION | | | REQUIRED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | |
|