| Plan Review Notes For Permit 05031134 |
| Permit Number |
05031134 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-25 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE SEE PLANS APPEAR TO BE | | | SIGNED WITH INITIALS. PLEASE SEE PLANS | | | MUSTBE SIGNED WITH LEGAL "SIGNATURE". | | | IF INDEED THIS IS LEGAL SIGNATURE, | | | PLEASE PROVIDE A SIGNED, DATED AND | | | SEALEDNOTORIZED LETTER PERTAINING TO | | | SIGNATURE. | | | | | | 2)NOTE: PLEASE SEE PANEL IL5 IS SHOWN AS | | | MLO WITHOUT A MAIN AND IS SHOWN COMING | | | DIRECTLY FROM TRANSFORMER. | | | PLEASE SEE A MAIN CIRCUIT BRKR IS | | | REQUIRED. 225.31,240.4,230.71,408.16 | | | | | | 3)NOTE: PLEASE SEE MISSING PANEL | | | SCHEDULE FOR CP. | | | PLEASE SHOW NEW CIRCUITING #'S AND | | | CORRELATE WITH PANEL SCHEDULES. | | | | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS WHICH | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|