2005-06-23 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WILL
 BE REQUIRED SHOULD THE DESIGN CAPACITY
 OF THE MULTIPLE AHU SYSTEMS HAVE THE
 DESIGN CAPACITY GREATER THAN 2,000 CFM.
 2001 FBC(M)606.2.2.
  