Plan Review Notes
Plan Review Notes For Permit 05031130
Permit Number 05031130
Review Stop E
Sequence Number 4
Notes
Date Text
2006-02-22 00:00:00*********** UNSAT 3RD REVIEW *********
  
 ** PLEASE SEE COMMENTS FROM TWO PREVIOUS
 REVIEWS WHICH WERE NOT CORRECTED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023 FOR MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS.
 PLEASE SEE MISSING CA/ EB # AS REQUIED.
 PLEASE SEE THIS HAS BEN REQUESTED ON TWO
 PREVIOUS REVIEWS.
  
 2)NOTE: PLEASE CORRELATE SCOPE OF WORK.
 PLEASE SEE PLASN INDICATE A NW SW BOARD,
 YET RISER SHOWS THIS AS EXISTING?
 PLEASE SEE STILL NO LOAD CALCULATIONS,
 PANEL SCHEDULES ETC HAVE BEEN SUBMITTED
 FOR REVIEW.
 215.5,220, 110.9,ETC
 NOTED ON BOTH PREVIOUS REVIEWS.
  
 3)NOTE: PLEASE SEE NOTES ON PLANS WHICH
 ARE CIRCILED WHICH ARE NOT ALL LISTED IN
 THE "NOTES" LEGEND? #8?
 215.5
  
 4)NOTE: PLEASE SEE NO OCPETC IS SHOWN
 FOR NEW FEED TO DISCONNECT TO"CH4MP",
 PLEASE SEE 240.21 , TAPS??
 240.4,310.16ETC.
 PREVIOUS REVIEW, PART OF NOTES FOR RISER
 AND NEW OCP, LOADS ETC.
  
 5)NOTE: PLEASE SEE VALUATION HAS STILL
 NOT BEEN INCREASED FOR SCOPE OF WORK
 SHOWN ON PLANS.
 PLEASE SEE WHAT PLANS SHOW AND
 APPLICATION SHOWS IS TWO DIFFERENT
 THINGS.
 PLEASE KNOW, AN ELECTRICAL PERMIT WILL
 BE REQUIRED FOR ELECTRICAL SCOPE OF
 WORK.
 FBC 104.6.5,104.2.1
  
 6)NOTE: PLEASE SEE AIC RATINGS FOR NEW
 DISCONNECTS ETC NOT SHOWN, ONLY FOR
 PANEL "CH4MP".
 110.9,215.5
  
 7)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 AND ATTACHED TO NOTES AND RE-SUBMITTIAL
 SHEET DATED 7/18/05 PERTAINING TO FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS THREE
 OR MORE TIMES.
 PLEASE SEE A 4X FEE HAS NOW BEEN
 ACCESSED AS REQUIRED PER FS FOR SAID
 REPEAT COMMENTS.
 THIS FEE IS BASED ON 4X THE PLAN REVIEW
 PORTION OF THE BASE PERMIT FEE.(30%)
 THE AMOUNT NOW OWED IS $980.00 AND SHALL
 BE PAID BEFORE RESUBMITTING PLANS FOR
 NEXT REVIEW. PLEASE, KNOW, IF ANY OF THE
 SAME COMMENTS ARE REPEAT COMMENTS ON
 NEXT REVIEW, THE FEE SHALL BE ACCESSED
 ONCE AGAIN AND PLANS SHALL BE FORWARDED
 TO THE STATE.
 PLEASE KNOW, ONE SET OF PLANS ARE BEING
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS, AND THE FBPE'S LEGAL CONSEL
 FOR REVIEW AND SAID MISSING REQUIRED
 CERTIFICATE OF AUTHORIZATIONLICENSE
 NUMBER AS REQUIRE BY DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. ONCE AGAIN AS NOTED ON BOTH
 PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE TO GO OVER
 COMMENTS OR QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW