| 2005-07-20 00:00:00 | ********* UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE SOME OF THE SAME NOTES FROM |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE MSSING INFORMATION |
| | REQUIRED ON TITLE BLOCK PER FAC |
| | 61G15-23.002. PLEASE SEE MISSING LICENSE |
| | # WHICH IS REQUIRED UNDER FS 471.023. |
| | THE CERTIFICATE OF AUTHORIZATION #? |
| | |
| | 2)NOTE: PLEASE CORRELATE PLANS. PLEASE |
| | SEE SHEET E-1 STILL SHOWS NEW |
| | SWICTHBOARD EQUIPMENT ETC, HOWEVER PANEL |
| | SCHEDULES ETC ARE NOT SUBMITTED AND DO |
| | NOT CORRELATE WITH THIS SCOPE OF WORK? |
| | PLEASE SEE A CIRCLED NOTE #8 ON ON PLAN, |
| | BUT IN "NOTE"? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE NOTE #2 ON PLANS |
| | MENTIONS TO "MODIFY" CHDP?? |
| | PLEASE VERIFY THIS, AS CHANGING OR |
| | MODIFICATION OF ANY LISTED PRODUCT OS |
| | NOT PERMITTED. |
| | PLEASE SEE 90.7, 110.3. |
| | |
| | 3)NOTE: PLEASE SEE NO PANEL SCHEDULE |
| | FOR CHDP. |
| | PLEASE SEE NO LOAD CALCULATIONS WERE |
| | SUBMITTED FOR ADDED LOADS TO CHDP OR |
| | MAIN SW BOARD. |
| | 215.5,220. |
| | |
| | 4)NOTE: PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL AND COMMENTS REPEATED FOR |
| | PLANS REVIEW. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |