2005-07-20 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME OF THE SAME NOTES FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: PLEASE SEE MSSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002. PLEASE SEE MISSING LICENSE
 # WHICH IS REQUIRED UNDER FS 471.023.
 THE CERTIFICATE OF AUTHORIZATION #?
  
 2)NOTE: PLEASE CORRELATE PLANS. PLEASE
 SEE SHEET E-1 STILL SHOWS NEW
 SWICTHBOARD EQUIPMENT ETC, HOWEVER PANEL
 SCHEDULES ETC ARE NOT SUBMITTED AND DO
 NOT CORRELATE WITH THIS SCOPE OF WORK?
 PLEASE SEE A CIRCLED NOTE #8 ON ON PLAN,
 BUT IN "NOTE"?
 215.5
  
 2)NOTE: PLEASE SEE NOTE #2 ON PLANS
 MENTIONS TO "MODIFY" CHDP??
 PLEASE VERIFY THIS, AS CHANGING OR
 MODIFICATION OF ANY LISTED PRODUCT OS
 NOT PERMITTED.
 PLEASE SEE 90.7, 110.3.
  
 3)NOTE: PLEASE SEE NO PANEL SCHEDULE
 FOR CHDP.
 PLEASE SEE NO LOAD CALCULATIONS WERE
 SUBMITTED FOR ADDED LOADS TO CHDP OR
 MAIN SW BOARD.
 215.5,220.
  
 4)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND COMMENTS REPEATED FOR
 PLANS REVIEW.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  