2005-10-14 00:00:00********* UNSAT **********
  
 PLEASE SEE NOTES BELOW FROM EXISTING
 "PROVISO" GIVEN AND NEW COMMENTS DUE TO
 CHANGES ON RISER DIAGRAM.
  
  
 1)NOTE: PLEASE SEE RECEPTS LABELED TO BE
 INSTALLED ABOVE CEILINGS IS NOT
 PERMITTED PER 400.8/410.30 ETC.
 PLEASE SEE THESE RECEPTS MUST BE "IN"
 CEILING, NOT ABOVE.
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 ON EXISITNG GUTTER FOR CONNECTION OF NEW
 METER/SERVICE.
 215.5,220
  
 3)NOTE: PLEASE SEE RISER SUBMITTED IS
 NOW SHOWING A NEW GUTTER, MAIN AND TWO
 NEW TENANT SPACES. PLEASE SEE ONE SHOWN
 AS FUTURE IS OK.
 PLEASE INDICATE IS WORK FOR OTHER MAIN
 DISCONNECTS/METERS ARE UNDER SEPARATE
 PERMITS.
 PLEASE INDICATE OF EXISTING.
 PLEASE SEE 60A DISCONNECT WITH 150A
 LOAD??
 PLEASE PROVIDE SIZE AND LOAD ON
 BUS-RISER.
  
 4)NOTE: PLEASE BE SURE ALL PLANS
 SUBMITTED CONTAIN THE RAISED SEAL AND
 ARE SIGNED AND DATED BY THE ENGINEER OF
 RECORD.
 FS 471.025
 PLEASE BE SURE THE RAISED SEAL IS CLEAR
 AND VISABLE WITH ALL INFORMATION ON SAID
 SEAL AS REQUIRED UNDER FAC 61G15-23.002
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  