| 2005-10-14 00:00:00 | ********* UNSAT ********** |
| | |
| | PLEASE SEE NOTES BELOW FROM EXISTING |
| | "PROVISO" GIVEN AND NEW COMMENTS DUE TO |
| | CHANGES ON RISER DIAGRAM. |
| | |
| | |
| | 1)NOTE: PLEASE SEE RECEPTS LABELED TO BE |
| | INSTALLED ABOVE CEILINGS IS NOT |
| | PERMITTED PER 400.8/410.30 ETC. |
| | PLEASE SEE THESE RECEPTS MUST BE "IN" |
| | CEILING, NOT ABOVE. |
| | |
| | 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | ON EXISITNG GUTTER FOR CONNECTION OF NEW |
| | METER/SERVICE. |
| | 215.5,220 |
| | |
| | 3)NOTE: PLEASE SEE RISER SUBMITTED IS |
| | NOW SHOWING A NEW GUTTER, MAIN AND TWO |
| | NEW TENANT SPACES. PLEASE SEE ONE SHOWN |
| | AS FUTURE IS OK. |
| | PLEASE INDICATE IS WORK FOR OTHER MAIN |
| | DISCONNECTS/METERS ARE UNDER SEPARATE |
| | PERMITS. |
| | PLEASE INDICATE OF EXISTING. |
| | PLEASE SEE 60A DISCONNECT WITH 150A |
| | LOAD?? |
| | PLEASE PROVIDE SIZE AND LOAD ON |
| | BUS-RISER. |
| | |
| | 4)NOTE: PLEASE BE SURE ALL PLANS |
| | SUBMITTED CONTAIN THE RAISED SEAL AND |
| | ARE SIGNED AND DATED BY THE ENGINEER OF |
| | RECORD. |
| | FS 471.025 |
| | PLEASE BE SURE THE RAISED SEAL IS CLEAR |
| | AND VISABLE WITH ALL INFORMATION ON SAID |
| | SEAL AS REQUIRED UNDER FAC 61G15-23.002 |
| | ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |