2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 DETAILS 3 & 4, THE FOLLOWING
 INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE:
 A) 11-4.16.2 CLEAR FLOOR SPACE (W/C)
 B) FLUSH CONTROLS 11-4.16.5
 C) FAUCETS 11-4.19.5 (LAV)
 2) SHT A-1 BREAK ROOM, A TURNING AREA IS
 REQUIRED TO COMPLY WITH 11-4.2.3 AND
 FIGURE 3(A) OR 3(B).
 3) SHT A-2 DETAILS 14 & 15 THE FOLLOWING
 INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE:
 A) KNEE CLEARANCE 11-4.24.3
 B) DEPTH OF SINK 11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH IS REQUIRED. MAXIMUM 19"
 UNDERNEATH THE SINK. CABINET DOORS
 CANNOT BE IN THE CLEAR FLOOR SPACE.
 D) EXPOSED PIPES & SURFACES 11-4.24.6
 E) FAUCETS 11-4.24.7
 4) SHT P-1 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(4).
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. IF A DRINKING FOUNTAIN IS
 AVAILABLE IN THE COMMON AREA OF THE
 BUILDING, PLEASE INDICATE ON PLANS.
 5) SHT P-2 WATER HEATER DETAIL. THE
 FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTICLE. EITHER A HUB DRAIN OR
 A FLOOR SINK WILL BE REQUIRED IF
 DRAINING THE PAN DRAIN AND/OR THE T&P
 VALVE TO SANT. SECTIONS 802.3 & 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]