| 2005-06-29 00:00:00 | ******** UNSAT ********** |
| | |
| | PLEASE SEE PLANS HAVE NOW COME IN WITH |
| | CHANGES FROM PREVIOUS PLANS SUBMITTED |
| | FOR REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE 110.26, 450.9, |
| | 450.13, 450.21 ETC. |
| | MINIMUM WORKING CLEARANCES ARE NOT |
| | REQUIRED IF THE EQUIPMENT IS SUCH THAT |
| | IT IS NOT LIKELY TO REQUIRE EXAMINATION, |
| | ADJUSTMENT, SERVICING, OR MAINTENANCE |
| | WHILE ENERGIZED. HOWEVER, ?SUFFICIENT? |
| | ACCESS AND WORKING SPACE ARE STILL |
| | REQUIRED BY THE OPENING PARAGRAPH OF |
| | 110.26, PLEASE SEE 450 AS NOTED ABOVE |
| | FOR MIN AREA. |
| | IF USEING SCALE ON PLANS, LESS THAN 9" |
| | IS SHOWN TO REACH DISC, ETC. |
| | |
| | 2)NOTE: PLEASE SHOW ATTACHMENT FOR |
| | TRANSFORMER GROUNDING. 250.30 |
| | PLEASE SEE NOTE MENTIONS TO BLDG |
| | SECONDARY GRND? PER APPLICABLE CODE. |
| | PLEASE SEE FBC 104.2.1, CODE SHALL NOT |
| | BE REFERENCED IN WHOLE OR IN PART FOR |
| | TECHNICAL AREAS. |
| | |
| | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |