Plan Review Notes
Plan Review Notes For Permit 05031124
Permit Number 05031124
Review Stop E
Sequence Number 3
Notes
Date Text
2005-06-29 00:00:00******** UNSAT **********
  
 PLEASE SEE PLANS HAVE NOW COME IN WITH
 CHANGES FROM PREVIOUS PLANS SUBMITTED
 FOR REVIEW.
  
 1)NOTE: PLEASE SEE 110.26, 450.9,
 450.13, 450.21 ETC.
 MINIMUM WORKING CLEARANCES ARE NOT
 REQUIRED IF THE EQUIPMENT IS SUCH THAT
 IT IS NOT LIKELY TO REQUIRE EXAMINATION,
 ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE ENERGIZED. HOWEVER, ?SUFFICIENT?
 ACCESS AND WORKING SPACE ARE STILL
 REQUIRED BY THE OPENING PARAGRAPH OF
 110.26, PLEASE SEE 450 AS NOTED ABOVE
 FOR MIN AREA.
 IF USEING SCALE ON PLANS, LESS THAN 9"
 IS SHOWN TO REACH DISC, ETC.
  
 2)NOTE: PLEASE SHOW ATTACHMENT FOR
 TRANSFORMER GROUNDING. 250.30
 PLEASE SEE NOTE MENTIONS TO BLDG
 SECONDARY GRND? PER APPLICABLE CODE.
 PLEASE SEE FBC 104.2.1, CODE SHALL NOT
 BE REFERENCED IN WHOLE OR IN PART FOR
 TECHNICAL AREAS.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  