2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A1 ACCESSIBLE TOILET ROOM DETAIL,
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A) 11-4.16.5 FLUSH CONTROLS
 B) HEIGHT & CLEARANCES 11-4.19.3 (29")
 C) EXPOSED PIPES & SURFACES 11-4.19.4
 D) FAUCEST 11-4.19.5
 E) MEASUREMENT FORM CENTERLINE OF LAV
 TO VANITY TO BE MIN. 15" TO CENTER ON
 30" DIMENSION OF CLEAR FLOOR SPACE. (SEE
 FIGURE 32).
 2) SUBMIT A DETAIL FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) SINK DEPTH 11-4.24.4
 D) CLEAR FLOOR SPACE 11-4.24.5 -
 FORWARD APPROACH REQUIRED. MAXIMUM 19"
 UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE.
 E) EXPOSED PIPES & SURFACES 11-4.24.6
 F) FAUCETS 11-4.24.7
 3) SHT P1 WATER RISER, FULL OPEN VALVES
 ARE REQUIRED ON EVERY WATER DOWN-FEED
 LINE. SECTION 606.1(4)
 4) SHT P1 INSTA-HOT WATER HEATERS SHALL
 BE LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS TO VERIFY. SECTION 303.4
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. IF A DRINKING FOUNTAIN IS
 AVAILABLE IN THE COMMON AREA PLEASE
 INDICATE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]