| 2005-03-24 00:00:00 | 1) PLANS DON'T SHOW THE LOCATIONS OF | | | AUDIBLE/VISUAL DEVICES. PLEASE SHOW THE | | | LOCATIONS, AND INDICATE IF THESE DEVICES | | | ARE EXISTING OR NEW. | | | | | | 2) PLEASE BE ADVISED THAT IN ADDITION TO | | | FAN SHUT DOWN, THE ACTIVATION OF ANY | | | DUCT SMOKE DETECTOR SHALL CAUSE THE FIRE | | | ALARM SYSTEM TO SOUND A GENERAL FIRE | | | ALARM. | | | | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|