| 2005-09-09 00:00:00 | DENIED |
| | SECOND REVIEW: |
| | |
| | 1. PLEASE SHOW ON PLAN BASIC WIND SPEED |
| | AS 140MPH.ARCHITECT OF RECORD TO |
| | INITIAL CHANGES ON PLANS. |
| | |
| | 2.ALL PRODUCT APPROVALS REQUIRE THE |
| | FOLLOWING TO BE ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 4.INCLUDE A ROOF SHEATHING NAILING |
| | SCHEDULE COMPLYING WITH WEST PALM BEACH |
| | AMMENDMENTS TO THE FBC 2306.1 |
| | NEW PAGE SUBMITTED SHALL HAVE SEAL AND |
| | SIGNATURE FROM ARCHITECT OF RECORD. |
| | ROOF SHEATHING IS STILL SHOWN AS 1/2" |
| | AND SHOULD BE 5/8". |
| | |
| | NOTE: TRUSS PLANS ARE NOT REQUIRED FOR |
| | REVIEW.PLEASE HAVE AT JOB SITE FOR |
| | INSPECTORS DURING ROOF FRAMING |
| | INSPECTIONS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |