| Plan Review Notes For Permit 05031046 |
| Permit Number |
05031046 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-22 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FORCODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}PLEASE INDICATE THE PANEL AND CIRCUIT | | | NUMBERS BEING USED. | | | | | | 2}INDICATE CONDUIT AND CONDUTOR SIZE AND | | | TYPE. | | | | | | 3}INDICATE OCP RATING. | | | | | | 4}THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT AND SIGN THEIR NAME | | | PER 104.2.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|