| Plan Review Notes For Permit 05031039 |
| Permit Number |
05031039 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) PER NOTE ON THE BACK OF THE | | | APPLICATION, SIGNATURE OF CONTRACTOR | | | SHAL BE NOTORIZED. | | | 2) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | SECTION 104.2.1. | | | 3) NO PERMIT PERTAINING TO A GENERATOR | | | SHALL BE ISSUED UNTIL AN APPLICATION FOR | | | THE GENERATOR, WITH A REVIEW FOR THE | | | GENERATOR BY BUILDING, ELECTRIC, | | | MECHANICAL, AND ZONING PLAN REVIEWERS. | | | THE BUILDING REVIEW WILL BE FOR SLAB AND | | | ANCHORING, (SUBMIT A DETAIL), ELECTRICAL | | | REVIEW WILL BE FOR THE TRANSFER SWITCH, | | | (SUBMIT MANUF. SPECIFICATION SHEETS - | | | MUST BE LISTED AND APPROVED), MECHANICAL | | | REVIEW FOR THE EXHAUST, (PROPER | | | CLEARANCES FROM OPENINGS IN HOUSES | | | INCLUDING ADJOINING), AND ZONING, | | | (SHOWING DISTANCE FROM PROPERTY LINE | | | ECT.). | | | 4) GAS PLAN OTHERWISE CODE COMPLIANT AND | | | WILL BE ISSUED UPON SATISFACTION OF | | | COMMENTS 1 THRU 3 ABOVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|