2005-04-13 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PREVIOUS REVIEW:
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - THE BTU RATING FOR THE
 GENERATOR HAS NOT BEEN PROVIDED. THIS IS
 REQUIRED FOR SIZING OF THE PIPING. ALSO
 THE BTU RATING FOR THE EXISTING WATER
 HEATER SHALL BE RECHECKED. PAST
 EXPERIANCE INDICATES MORE BTU'S FOR A
 WATER HEATER THAN THE 3.200 INDICATED.
 THIS WILL BE VERIFIED BY THE FIELD
 INSPECTOR.
 7) AN APPLICATION FOR A GENERATOR SHALL
 BE SUBMITTED, AS A BUILDING REVIEW,
 ELECTRICAL REVIEW, ZONING REVIEW, AND
 MECHANICAL REVIEW WILL BE REQUIRED.
 (THIS IS A CITY REQUIREMENT).
 ****************NEW COMMENT************
 1B) UPON READING THE MANUFACTURE
 INFORMATION SUBMITTED, IT INDICATES THAT
 THE MAXIMUM GAS PRESSURE FOR THE
 GENERATOR SHALL BE 1/4 LB. AND 1/2 LB IS
 PROVIDED. A REGULATOR SHALL BE REQUIRED.
 SUBMIT MANUF. SPECIFICATION FOR
 REGULATOR AND SHOW ON ISOMETRIC THE
 REGULATOR DOWNSTREAM OF THE SHUT OFF
 VALVE FOR THE GENERATOR.
  