| 2005-04-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEW: |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - THE BTU RATING FOR THE |
| | GENERATOR HAS NOT BEEN PROVIDED. THIS IS |
| | REQUIRED FOR SIZING OF THE PIPING. ALSO |
| | THE BTU RATING FOR THE EXISTING WATER |
| | HEATER SHALL BE RECHECKED. PAST |
| | EXPERIANCE INDICATES MORE BTU'S FOR A |
| | WATER HEATER THAN THE 3.200 INDICATED. |
| | THIS WILL BE VERIFIED BY THE FIELD |
| | INSPECTOR. |
| | 7) AN APPLICATION FOR A GENERATOR SHALL |
| | BE SUBMITTED, AS A BUILDING REVIEW, |
| | ELECTRICAL REVIEW, ZONING REVIEW, AND |
| | MECHANICAL REVIEW WILL BE REQUIRED. |
| | (THIS IS A CITY REQUIREMENT). |
| | ****************NEW COMMENT************ |
| | 1B) UPON READING THE MANUFACTURE |
| | INFORMATION SUBMITTED, IT INDICATES THAT |
| | THE MAXIMUM GAS PRESSURE FOR THE |
| | GENERATOR SHALL BE 1/4 LB. AND 1/2 LB IS |
| | PROVIDED. A REGULATOR SHALL BE REQUIRED. |
| | SUBMIT MANUF. SPECIFICATION FOR |
| | REGULATOR AND SHOW ON ISOMETRIC THE |
| | REGULATOR DOWNSTREAM OF THE SHUT OFF |
| | VALVE FOR THE GENERATOR. |
| | |