2005-12-21 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE THE 1-POLE 20A
 CIRCUIT FOR THE POOL LTS EXCEED THE MAX
 PF 1920VA PERMITTED ON A 20A CIRCUIT.
 PLEASE VERIFY LOAD.
 240.4, 310.16
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL SPACE IN KITCHEN. 210.52
  
 3)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THAT SHOWN ON
 PANEL SCHEDULE AND ADJUST LOADS AS
 NEEDED.
 220.4B3
  
 4)NOTE: PLEASE SEE NEW INSTA-HOT
 INDICATED ON PLANS, BUT NOT ON PANEL
 SCHEDULE OR LOAD CALCS.
 PLEASE ADJUST.
 215.5
  
 5)NOTE: PLEASE SEE LT FIXTURE IN BEDRM
 CLOSET #4, THIS SEEMS TO BE TOO CLOSE TO
 SHELVING PER 410.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  