| Plan Review Notes For Permit 05030986 |
| Permit Number |
05030986 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-12-21 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE SEE THE 1-POLE 20A | | | CIRCUIT FOR THE POOL LTS EXCEED THE MAX | | | PF 1920VA PERMITTED ON A 20A CIRCUIT. | | | PLEASE VERIFY LOAD. | | | 240.4, 310.16 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT FOR 2' | | | OF WALL SPACE IN KITCHEN. 210.52 | | | | | | 3)NOTE: PLEASE CORRELATE THE NUMBER OF | | | RECESSED LTS ON PLANS WITH THAT SHOWN ON | | | PANEL SCHEDULE AND ADJUST LOADS AS | | | NEEDED. | | | 220.4B3 | | | | | | 4)NOTE: PLEASE SEE NEW INSTA-HOT | | | INDICATED ON PLANS, BUT NOT ON PANEL | | | SCHEDULE OR LOAD CALCS. | | | PLEASE ADJUST. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE LT FIXTURE IN BEDRM | | | CLOSET #4, THIS SEEMS TO BE TOO CLOSE TO | | | SHELVING PER 410.8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASEDO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|