Plan Review Notes For Permit 05030986
Permit Number 05030986
Review Stop B
Sequence Number 3
Notes
Date Text
2005-06-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE GROUND FLOOR ENGINEERING
 CALCULATIONS FOR SOME OF THE BEAMS SAY
 "NO GOOD" INSTEAD OF "OK".IT APPEARS
 THAT THOSE ITEMS ARE NOT OK.PLEASE
 ADDRESS.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 3.)SEE THE PREVIOUS LIST, ITEM 5C.
 THE DESIGN PRESSURE FOR THE 36X47 AND
 53X95 BUTT GLASS OPENINGS IS +31/-41 ON
 SHEET A2.THE ENGINEERING HAS A DESIGN
 PRESSURE LIMITATION OF +30.1/-32.8.
  
 4.)PROVIDE TWO COPIES OF THE MULLION
 PRODUCT APPROVALS.ONLY ONE COPY WAS IN
 THE PACKAGE.