Plan Review Notes
Plan Review Notes For Permit 05030986
Permit Number 05030986
Review Stop B
Sequence Number 2
Notes
Date Text
2005-05-06 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT. (IT'S EXPIRED).
  
 3- GROUND FLOOR ENGINEERING CALCULATIONS
 CAN'T BE ACCEPTED BECAUSE PROGRAM SHOWS
 THAT CALCULATIONS ARE DONE USING ASCE
 7-02. EDITION ADOPTED BY FBC 2001 IS
 ASCE 7-98. SEE CHAPTER 35 FBC 2001.
  
 4- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE WHICH WAS REVISED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 CONNECTOR HTA16 WAS REVISED TO USE 10
 NAILS. ADDING MORE NAILS WILL NOT
 INCREASE THE UPLIFT CAPACITY OF THE
 CONNECTOR. REVISE AS REQUIRED.
  
 5- BUTT GLAZING SYSTEM:
 A) THERE ARE 2 ASSEMBLIES SYSTEMS SHOWN
 ON PLANS. ONLY ONE SUBMITTED AND IT
 DOESN'T MATCH PLANS.
  
 B) NEED COMPLETE ENGINEERING ANALYSIS,
 DRAWINGS AND CALCULATIONS. SEE SECTION
 2406.2 FBC 2001.
 **NOTE: DADE COUNTY NOA SUBMITTED CANN'T
 BE USED BECAUSE THE INSTALLATION IS NOT
 THE SAME AS APPROVED ON SUCH NOA.
 ENGINEER NEEDS TO PRODUCE COMPLETE SET
 OF DRAWINGS WITH COMPLETE SPECIFICATIONS
 FOR ASSEMBLIES SHOWN ON PLANS.
  
 C) DESIGN PRESSURES DON'T MEET THE
 DESIGN PRESSURES CALCULATED ON PLANS.
  
 D) SIZE OF ASSEMBLY TESTED IS SMALLER
 THAN THOSE SHOWN ON PLANS. THEREFORE, IT
 DOESN'T COVER THEM.
  
 6- PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE FOR THE FOLLOWING USP
 CONNECTORS: UMH358 AND TDX8.
  
 7- SHUTTERS DRAWINGS NEED TO BE SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED
 BY HIM ON GENERAL NOTE #11(E).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  