Plan Review Notes
Plan Review Notes For Permit 05030986
Permit Number 05030986
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
  
 2- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS. NEED RE-RECORDED ONE.
  
 3- PROVIDE ENGINEERING CALCULATIONS FOR
 DESIGN PRESSURES AT ALL EXTERIOR
 OPENINGS SHOWING HOW PRESSURES GIVEN ON
 WINDOW AND DOOR SCHEDULES WERE OBTAINED.
 SEE TABLES 1606.2B AND 1606.2E FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4- A) GROUNDFLOOR ENGINEERING LETTER
 SAYS THAT STRUCTURE WAS REVIEWED FOR
 140MPH DESIGN SPEED ANDEXPOSURE C.
 DESIGN PRESSURES CALCULATED ON PLANS DO
 NOT CORRESPOND TO EXPOSURE C CATEGORY.
 REVISE AS REQUIRED AND PROVIDE DESIGN
 PRESSURES CALCULATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) GROUND FLOOR ENGINEERING LETTER SAYS
 THAT HE IS THE ENGINEER OF RECORD.
 ENGINEER OF RECORD IS THE ONE WHO SEALS
 THE DRAWINGS AND SPECS. SEE CHAPTER 471
 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD
 AND PROVIDE HIS INFORMATION ACCORDINGLY.
  
 5- A) UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE THAT WAS UPDATED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS AND CALCS THAT COMPLY WITH SEC.
 1609.4.3 FBC FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED
 AND PUBLISHED BY THE MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 B) USP RT20T CONNECTOR RESISTS NOT
 LATERAL LOADS. HOW IS THE TRUSS
 SUPPORTED TO RESIST LATERAL LOADS?. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) USP USC64 DON'T RESIST THE LOADS
 CALCULATED ON GIRDER TRUSS AT MASTER
 BEDROOM. SEE COMMENTS ON PLANS AND
 RETURN REVIEWED SET AFTER CHANGES ARE
 DONE TO ORIGINAL DRAWINGS TO EXPEDITE
 REVIEW.
  
 D) SPECIFY TRUSS CONNECTOR FOR TRUSSES
 BETWEEN COVERED PATIO AND LIVING ROOM.
 SEE PLANS FOR COMMENTS.
  
 E) USP UMH358 DOESN'T WORK FOR 4 PLY
 MIN. GIRDER TRUSS SPECIFIED ON ROOF
 FRAMING PLAN. REVISE AS REQUIRED.
  
 6- PROVIDE BBQ LISTING AND SPECS SEC.
 2808 FBC 2001.
 **NOTE; BBQ SPECS SAY THAT BBQ ARE
 DESIGNED FOR OUTDOOR USE ONLY. NEED
 MANUFATURER SPECIFICATIONS CERTIFYING
 THAT BBQ GRILLS ARE SAFE TO BE INSTALLED
 IN THE PORCH.
  
 7- BUTT GLAZING ASSEMBLIES: A) PROVIDE
 COMPLETE ENGINEERING ANALYSIS AND
 CALCULATIONS REQUIRED BY SEC. 2406.2 FBC
 2001. INCLUDING GLASS THICKNESS.
 **NOTE: DADE COUNTY NOA'S CANN'T BE USED
 IF THEY ARE ALTERED.
  
 B) THERE ARE TWO DIFFERENT BUTT GLAZING
 ASSEMBLIES. SEE PLANS. NEED ANALYSIS FOR
 BOTH ASSEMBLIES.
  
 C) PROVIDE CALCULATIONS FOR DESIGN
 PRESSURESAT OPENINGS WERE ASSEMBLIES
 ARE GOING TO BE INSTALLED. THIS IS PART
 OF THE ENGINEERING ANALYSIS FOR SITE
 SPECIFIC APPLICATIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8- ROOF TILE: PROVIDE REPORT THAT WAS
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 SBCCI REPORT, NOT DADE COUNTY NOA.
  
 9- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR ALL
 CONNECTORS SPECIFIED ON THE TRUSS ANCHOR
 SCHEDULE.
  
 10- STORM SHUTTERS: A) DADE COUNTY NOA
 SUBMITTED IS EXPIRED.
  
 B) GENERAL NOTE 11(E) REQUIRES DRAWINGS
 TO BE SIGNED AND SEALED BY THE ENGINEER.
  
 11- FLORIDA PRODUCT APPROVAL FOR FIXED
 WINDOWS IS NOT LEGIBLE.
  
 12- MULLIONS: CLEARLY INDICATE ON
 DRAWINGS SPECIFIC MULLION SIZE AND
 ANCHORING TO VERIFY ADEQUACY ACCORDING
 TO THE CALCULATED DESIGN PRESSURES.
 **NOTE: PAY ATTENTION TO LARGE AREAS
 LIKE FAMILY ROOM AND DINING ROOM
 ASSEMBLIES. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001. SEE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.