Plan Review Notes
Plan Review Notes For Permit 05030960
Permit Number 05030960
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 FROM PREVIOUS LIST; COMMENTS NOT
 ADDRESSED:
  
 1.)PROVIDE A TITLE BLOCK ON SHEETS E1F
 AND S1E.THE SEAL IS ILLEGIBLE.TITLE
 BLOCK TO INCLUDE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.
  
 2.) "FRANK W. NEAL & ASSOC" IS REQUIRED
 TO HAVE AN ENGINEERING CERTIFICATE OF
 AUTHORIZATION.INCLUDE THE NUMBER AS
 REQUIRED ON THE TITLE BLOCK.
  
  
 3.)SEAL STRUCTURAL AND ELECTRIC
 SHEETS.THE COVER SHEET ONLY OF
 CALCULATIONS CAN BE SEALED IN LIEU OF
 SEALING EACH SHEET BUT ALL ENGINEERED
 DETAILS SHOWING CODE COMPLIANCE MUST BE
 SEALED WITH A TITLE BLOCK.
  
 4.)PREVIOUS LIST ITEM #3 REQUESTED
 THAT INFORMATION ABOUT THE EXISTING
 BUILDING BE PROVIDED (BUILDING TYPE).
 THIS ITEM HAS NOT BEEN ADDRESSED BUT THE
 ENGINEER HAS ADVISED ME (BY TELEPHONE
 CONVERSATION) THAT THIS IS A TYPE II
 BUILDING.SEE FBC1511.5.
  