Plan Review Notes
Plan Review Notes For Permit 05030960
Permit Number 05030960
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-25 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE ANY LIGHTNING
 PROTECTION MUST CONFORM TO UL96A AND
 NFPA-780.
 PLEASE INCLUDE ALL INFORMATION PER ABOVE
 FOR REVIEW.
 PLEASE ALSO SEE AN ELECTRICLA PERMIT
 WILL BE REQUIRED FOR SYSTEM.
  
 2)NOTE: PLEASE SEE MISSING TITLE BLOCK
 INFORMATION AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  