| Plan Review Notes For Permit 05030907 |
| Permit Number |
05030907 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-07 00:00:00 | 1) THE MINIMUM WIDTH OF ACCESS MUST BE A | | | MINIMUM OF 20 FEET CLEAR UNOBSTRUCTED | | | WIDTH TO ACCOMODATE EMERGENCY VEHICLE | | | RESPONSE. | | | | | | 2) NEW ELECTRIC GATE INSTALLATIONS ARE | | | REQUIRED TO OPERATE BY KNOX KEY SYSTEM | | | WITH FAIL SAFE MECHANISM IN THE EVENT OF | | | POWER FAILURE TO THE GATE DRIVER. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|