Plan Review Notes
Plan Review Notes For Permit 05030903
Permit Number 05030903
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-23 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE.
 PER 210.52D, 210.11C3
  
 2} NOTE THAT THE BEDROOM OUTLETS MUST
 COMPLY WITH 210.12, INDICATE ON PANEL
 SCHEDULE. THE EXISTING PANEL WILL
 PROBABLTY NOT ALLOW FOR THIS.
  
 3} SEE CHAPTER 34 FBC FOR GFI AND SMOKE
 DETECTOR REQUIREMENTS.
  
 4} THE WINDOW A/C SHOWN IN THE ADDITION
 IS NOT SHOWN IN THE CALCULATION. SEE
 220.31(B).
  
 5} RECEPTACLE SPACING IN THE ADDED ROOM
 MUST COMPLY WITH 210.52(A)(1) & (2).
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT THEIR NAME AND SIGN
 THE PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved