| Plan Review Notes For Permit 05030903 |
| Permit Number |
05030903 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-23 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE LIST ALL THE REQ'D DEDICATED | | | BATH(S) CIRCUIT(S) ON PANEL SCHEDULE. | | | PER 210.52D, 210.11C3 | | | | | | 2} NOTE THAT THE BEDROOM OUTLETS MUST | | | COMPLY WITH 210.12, INDICATE ON PANEL | | | SCHEDULE. THE EXISTING PANEL WILL | | | PROBABLTY NOT ALLOW FOR THIS. | | | | | | 3} SEE CHAPTER 34 FBC FOR GFI AND SMOKE | | | DETECTOR REQUIREMENTS. | | | | | | 4} THE WINDOW A/C SHOWN IN THE ADDITION | | | IS NOT SHOWN IN THE CALCULATION. SEE | | | 220.31(B). | | | | | | 5} RECEPTACLE SPACING IN THE ADDED ROOM | | | MUST COMPLY WITH 210.52(A)(1) & (2). | | | | | | 6} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT THEIR NAME AND SIGN | | | THE PLANS PER 104.2.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|