| 2005-04-12 00:00:00 | DENIED: | | | PLAN SHEET M1 INDICATES THE SUPPLY | | | DIFFUSER WILL BE DIRECTED AWAY FROM THE | | | SMOKE DETECTOR.IN ACCORDANCE WITH NFPA | | | 72 AND NFPA 101, SMOKE DETECTORS ARE TO | | | BE INSTALLED IN ACCORDANCE TO THE | | | MANUFACTURERS SPECIFICATIONS AND NOT | | | LOCATED WITHIN 3 FT OF THE SUPPLY AND 5 | | | FT FROM A RETURN.SMOKE DETECTOR | | | SPACINGSHALL BE BASED ON TABLE | | | 2-3.6.6.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|