Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 9
Notes
Date Text
2006-06-29 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE SEE SPECS FOR NEW STEAM
 UNIT SHALL INDICATE A LISTING FROM A
 NRTL.
 PLEASE SEE PICTURES ARE SUBMITTED
 INDICATING THIS AND SHALL BE VERIFIED ON
 THE FIELD ASTHE SHEETS SUBMITTED DO
 NOT INDICATE ANY LISTING.
 **IF THIS UNIT IS NOT LISTED, IT MAY NOT
 BE INSTALLED.110.3
  
 PLEASE SEE SPECS MENTIONS NOT TO PLACE
 GFI PROTECTION *AS REQUIRED PER NEC
 210.8)??
 PLEASE SEE 210.8,680, IF GFI PROTECTION
 IS NOT INSTALLED, UNIT CAN NOT BE USED.
 PLEASE CLEALRY INDICATE WHICH UNIT IS
 BEING INSTALLED ON NEW SPECS.
  
 2) NOTE: PLEASE SEE UNIT IS NOT SHOWN ON
 PANEL SCHEDULE, ADDED TO LOAD(S)ETC.
 215.5,220.31B
 PLEASE SEE REVISEDPLANS FROM THE
 DESIGN PROFESSIONAL WERE NOT SUBMITTED
 FOR REVIEW .
 PLEASE SEE THAT ALL PLANS MUST BE
 REVISED ANDSUBMITTED.
 106.1.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  