| 2006-06-29 00:00:00 | ****** UNSAT ******** | | | | | | 1) NOTE: PLEASE SEE SPECS FOR NEW STEAM | | | UNIT SHALL INDICATE A LISTING FROM A | | | NRTL. | | | PLEASE SEE PICTURES ARE SUBMITTED | | | INDICATING THIS AND SHALL BE VERIFIED ON | | | THE FIELD ASTHE SHEETS SUBMITTED DO | | | NOT INDICATE ANY LISTING. | | | **IF THIS UNIT IS NOT LISTED, IT MAY NOT | | | BE INSTALLED.110.3 | | | | | | PLEASE SEE SPECS MENTIONS NOT TO PLACE | | | GFI PROTECTION *AS REQUIRED PER NEC | | | 210.8)?? | | | PLEASE SEE 210.8,680, IF GFI PROTECTION | | | IS NOT INSTALLED, UNIT CAN NOT BE USED. | | | PLEASE CLEALRY INDICATE WHICH UNIT IS | | | BEING INSTALLED ON NEW SPECS. | | | | | | 2) NOTE: PLEASE SEE UNIT IS NOT SHOWN ON | | | PANEL SCHEDULE, ADDED TO LOAD(S)ETC. | | | 215.5,220.31B | | | PLEASE SEE REVISEDPLANS FROM THE | | | DESIGN PROFESSIONAL WERE NOT SUBMITTED | | | FOR REVIEW . | | | PLEASE SEE THAT ALL PLANS MUST BE | | | REVISED ANDSUBMITTED. | | | 106.1.2 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|