| Plan Review Notes For Permit 05030779 |
| Permit Number |
05030779 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2006-06-12 00:00:00 | ****** UNSAT ******** | | | | | | 1) NOTE: PLEASE SEE SPECS FOR NEW STEAM | | | UNIT SHALL INDICATE A LISTING FROM A | | | NRTL. | | | IF THIS UNIT IS NOT LISTED, IT MAY NOT | | | BE INSTALLED.110.3 | | | PLEASE SEE SPECS SUBMITTED INDICATE UNIT | | | AS 3-PHASE, YET SERVICE IS NOT? | | | PLEASE SEE SPECS MENTIONS NOT TO PLACE | | | GFI PROTECTION *AS REQUIRED PER NEC | | | 210.8)?? | | | PLEASE SEE 210.8,680, IF GFI PROTECTION | | | IS NOT INSTALLED, UNIT CAN NOT BE USED. | | | PLEASE CLEALRY INDICATE WHICH UNIT IS | | | BEING INSTALLED ON NEW SPECS. | | | | | | 2) NOTE: PLEASE SEE UNIT IS NOT SHOWN ON | | | PANEL SCHEDULE, ADDED TO LOAD(S)ETC. | | | 215.5,220.31B | | | | | | 3) NOTE: PLEASE SEE PREVIOUS PLANS WERE | | | REDLINED FOR MISSING FOOTER STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | PLEASE INDICATE AND SIZE AS EXISTING GEC | | | IS SHOWN ON RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|