| 2006-03-01 00:00:00 | ELEC IN FOR REVIEW, ARCHITECT TO CALLED |
| | ON 3/2 FOR CORRECTIONS. |
| | ***** UNSAT ********* |
| | |
| | |
| | |
| | 1)NOTE; PLEASE SEE OCP FOR MAINS A AND B |
| | HAVE NOW BEEN REMOVED FROM METER/MAIN. |
| | PLEASE INDICAT ETH OCP FOR BOTH SUB |
| | PANELS. (200A?) |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE INDICAT EOF THE SUB PANEL |
| | "A" AND "B" ARE MLO? OR MCB? |
| | (MLO)? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY |
| | TO BE 1500VA .220.16, 210.11C |
| | |
| | 4)NOTE: PLEASE SEE BATH(S) CIRCUIT(S) |
| | ARE NOW BEING SHOWN AS 15A? |
| | PLEASE SEE 210.11C3, #12, 20A MIN. |
| | |
| | 5)NOTE: PLEASE SE ALL CONDUCTOR SIZES |
| | HAVE NOW BEEN REMOVED FROM PANEL |
| | SCHEDULES?? |
| | 215.5 PLEASE SHOW MIN PER 240.4,310.16 |
| | |
| | 6)NOTE: PLEASE SEE MISSING EGRESS LT AT |
| | FRONT DOOR.210.70,LS101 7.8 |
| | |
| | 7)NOTE: PLEASE VERIFY THE GDO HP RATING |
| | , THIS CAN BE REDLINED, HOWEVER IF KNOWN |
| | AT THIS TIME,PLEASE SEE TABLE 430.148. |
| | PLANS SHOW TWO DOORS WITH ONLY ONE |
| | CIRCUIT? |
| | |
| | 8)NOTE: PLEASE SEE SMALL APPLIANCE |
| | CIRCUITS NOW SHOWN AT 1200VA, PLEASE SEE |
| | 220.16, 210.52B1 FOR MIN VA TO BE 1500. |
| | |
| | ** PLEASE SUBMIT THE ABOVE REVISIONS FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |