Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 6
Notes
Date Text
2006-03-01 00:00:00ELEC IN FOR REVIEW, ARCHITECT TO CALLED
 ON 3/2 FOR CORRECTIONS.
 ***** UNSAT *********
  
  
  
 1)NOTE; PLEASE SEE OCP FOR MAINS A AND B
 HAVE NOW BEEN REMOVED FROM METER/MAIN.
 PLEASE INDICAT ETH OCP FOR BOTH SUB
 PANELS. (200A?)
 215.5
  
 2)NOTE: PLEASE INDICAT EOF THE SUB PANEL
 "A" AND "B" ARE MLO? OR MCB?
 (MLO)?
 215.5
  
 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY
 TO BE 1500VA .220.16, 210.11C
  
 4)NOTE: PLEASE SEE BATH(S) CIRCUIT(S)
 ARE NOW BEING SHOWN AS 15A?
 PLEASE SEE 210.11C3, #12, 20A MIN.
  
 5)NOTE: PLEASE SE ALL CONDUCTOR SIZES
 HAVE NOW BEEN REMOVED FROM PANEL
 SCHEDULES??
 215.5 PLEASE SHOW MIN PER 240.4,310.16
  
 6)NOTE: PLEASE SEE MISSING EGRESS LT AT
 FRONT DOOR.210.70,LS101 7.8
  
 7)NOTE: PLEASE VERIFY THE GDO HP RATING
 , THIS CAN BE REDLINED, HOWEVER IF KNOWN
 AT THIS TIME,PLEASE SEE TABLE 430.148.
 PLANS SHOW TWO DOORS WITH ONLY ONE
 CIRCUIT?
  
 8)NOTE: PLEASE SEE SMALL APPLIANCE
 CIRCUITS NOW SHOWN AT 1200VA, PLEASE SEE
 220.16, 210.52B1 FOR MIN VA TO BE 1500.
  
 ** PLEASE SUBMIT THE ABOVE REVISIONS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]