| 2006-02-08 00:00:00 | *** REVISIONS UNSAT 2ND REVIEW ****** |
| | |
| | ** SOME NOTES FROM PREVIOUS REVIEW. |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER WITH |
| | PANELS SUBMITTED. PLEASE SEE RISER SHOW |
| | A2 AS A 400A MCB PANEL WITH 2-200A BRKRS |
| | FOR SUB PANELS "B" AND "C" WITH TWO |
| | ADDITIONAL TWO POLEBRANCHCIRCUITS? |
| | PLEASE SEE RISER MENTIONS ONLY |
| | 4-CIRCUITS, PANEL SCHEDULE FOR PANEL A2 |
| | MENTIONS 6-SPACES. |
| | ??? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE ACC#1 SHOWN ON |
| | SCHEDULE FOR PANEL A2, HOWEVER RISER |
| | SHOWS THIS ACC UNIT #1 BEING FED FROM |
| | PANEL"B"?? |
| | PLEASE CORRELATE. |
| | |
| | 3)NOTE: PLEASE SEE AREAS: LOGGIA AND |
| | DINING RM WHICH WILL REQUIRE A MIN OF |
| | SOME TYPE OF LT FIXTURE FOR MEANS OF |
| | EGRESS. LS 101 7.8, NFPA-70 210.70. |
| | PLEASE SEE THESE AREAS ARE REDLINED. |
| | |
| | 4)NOTE: PLEASE VERIFY SEC'S WHICH ARE |
| | NOTED TO FPL HAND-HOLE AND ARE NOW TO BE |
| | PER FPL? |
| | PLEASE VERIFY THIS WITH THE FPL REP, AS |
| | IT HAS BECOME TO THE ATTENTION OF THIS |
| | OFFICE, SEC'S FROM THE FPL HAND-HOLE TO |
| | THE DWELLING SERVICE LOCATION IS THE |
| | RESPONSIBILITY OF THE OWNER> |
| | PLEASE VERIFY AS NOT TO HAVE TO REVISE |
| | THE PLANS AT A LATER DATE IF INDEED |
| | THESE SEC'S ARE OWNER INSTALLED. |
| | SIZING WILL BE PER NEC IF THIS IS THE |
| | CASE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |