Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 5
Notes
Date Text
2006-02-08 00:00:00*** REVISIONS UNSAT 2ND REVIEW ******
  
 ** SOME NOTES FROM PREVIOUS REVIEW.
  
  
 1)NOTE: PLEASE CORRELATE RISER WITH
 PANELS SUBMITTED. PLEASE SEE RISER SHOW
 A2 AS A 400A MCB PANEL WITH 2-200A BRKRS
 FOR SUB PANELS "B" AND "C" WITH TWO
 ADDITIONAL TWO POLEBRANCHCIRCUITS?
 PLEASE SEE RISER MENTIONS ONLY
 4-CIRCUITS, PANEL SCHEDULE FOR PANEL A2
 MENTIONS 6-SPACES.
 ???
 215.5
  
 2)NOTE: PLEASE SEE ACC#1 SHOWN ON
 SCHEDULE FOR PANEL A2, HOWEVER RISER
 SHOWS THIS ACC UNIT #1 BEING FED FROM
 PANEL"B"??
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE AREAS: LOGGIA AND
 DINING RM WHICH WILL REQUIRE A MIN OF
 SOME TYPE OF LT FIXTURE FOR MEANS OF
 EGRESS. LS 101 7.8, NFPA-70 210.70.
 PLEASE SEE THESE AREAS ARE REDLINED.
  
 4)NOTE: PLEASE VERIFY SEC'S WHICH ARE
 NOTED TO FPL HAND-HOLE AND ARE NOW TO BE
 PER FPL?
 PLEASE VERIFY THIS WITH THE FPL REP, AS
 IT HAS BECOME TO THE ATTENTION OF THIS
 OFFICE, SEC'S FROM THE FPL HAND-HOLE TO
 THE DWELLING SERVICE LOCATION IS THE
 RESPONSIBILITY OF THE OWNER>
 PLEASE VERIFY AS NOT TO HAVE TO REVISE
 THE PLANS AT A LATER DATE IF INDEED
 THESE SEC'S ARE OWNER INSTALLED.
 SIZING WILL BE PER NEC IF THIS IS THE
 CASE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]