| 2006-05-17 00:00:00 | ******REV DENIED****** |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING REVISION: |
| | |
| | 1. PER 104.2.1 REQUIREMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | NOTE: THE SANITARY RISER DIAGRAM |
| | INDICATED ON SHEET M-2 DOES NOT REFLECT |
| | THE FLOOR PLAN. THERE ARE 3 BATHROOMS |
| | AND A BAR LOCATED ON THE SECOND FLOOR |
| | BUT ALL THE PLUMBING INDICATED ON THE |
| | SANITARY RISER DIAGRAM IS ON THE FIRST |
| | FLOOR. PLEASE CORRECT AND SHOW THE |
| | SANITARY SOIL AND WASTE STACKS TO THE |
| | SECOND FLOOR PLUMBING IN BATHROOM #2 AND |
| | 3 ROOM #17, BATHROOM #4 ROOM #21, |
| | BATHROOM #5 ROOM #29 AND THE BAR IN ROOM |
| | #27. |
| | 2. 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK. PLEASE INDICATE |
| | CLEANOUTS ON CORRECTED DRAWING. |
| | 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | PLEASE INDICATE CLEANOUT ON DRAWING. |
| | 708.10 ACCESS. ACCESS SHALL BE PROVIDED |
| | TO ALL CLEANOUTS. NOTE CLEANOUT LOCATION |
| | ON WASHING MACHINE PLEASE INDICATE THIS |
| | ON CORRECTED DRAWING. |
| | |
| | END OF COMMENTS: |
| | |