Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 4
Notes
Date Text
2005-12-19 00:00:00******* UNSAT ***********
  
  
 PLEASE SEE SOME ITEMS REDLINED FROM
 PREVIOUS REVIEW(S).
  
 1)NOTE: PLEASE SEE NFPA-70, NFPA-101
 210.70, 7.8 WHICH REQUIRES A MIN CONTROL
 AND EGRESS LIGHTING.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 ONLY INDICATE A J-BOX, WHERE A MIN
 LIGHTING SOURCE IS REQUIRED.
  
 2)NOTE: PLEASE SEE MASTER BEDROM SD IS
 REQUIRED TO BE WITHIN 3' OF THE PEAK ON
 A SLOPED CEILING.
 NFPA-72 11.8.3.5
  
 3)NOTE: PLEASE SEE MIN LIGHTING,AND
 RECEPT(S) FOR AHU'S, 210.63,210.70
 PLEASE ALSO VERIFY IF THE AHU ON FIRST
 FLR IS IN MASTER CLOSET, ALSO PLEASE
 VERIFY THE THERE IS NO OCP AT THIS
 DISCONNECT SHOWN ONPLANS. 240.24
 110.26 ETC.
  
 4)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER
 250.66. 1/0 MIN
 SERVICE RISER HAS BEEN ADJUSTED.
  
 5)NOTE: PLEASE ALSO SEE SERVICE IS NOW
 SHOWN AS 400A'S, HOWEVER SEC'S FROM
 METER TO FPL HANDHOLE IS ONLY RATED AT
 200A'S.
 PLEASE SEE 310.15B6, 310.16
  
 6)NOTE: PLEASE VERIFY THE 2-200A
 BREAKERS SHOWN ON METER/MAIN SCHEDULE,
 PLEASE SEE BOTH DO NOT SEEM TO BE LISTED
 ONTHE SCHEDULE? ARE THESE ABOVE THE
 6-SPACES?
  
 7)NOTE: PLEASESEE POSSIBLE MISSING GFI
 FROM KITCHEN COUNTERSPACE. PLEASE SEE
 WHAT APPEARS TO BE 12" SPACE REDLINE DON
 PLANS.
 210.52C1
  
 8)NOTE: PLEASE SEE RISER SHOWS POOL
 PANEL BEING FED FROM PANEL "B" , HOWEVER
 PANEL SCHEDULE "B" DOES NOT INCLUDE POOL
 PANEL, YET METER/MAIN SCHEDULE DOES.
 PLEASE CORRELATE.
 215.5
  
 9)NOTE: PLEASE INDICATE IF THE LOAD
 SHOWN FOR POOL PUMP IS ALEADY FIGURED
 FOR CONTINUOUS LOAD. ?
 PLEASE SEE 215.3, 230.42 ETC WHICH
 REQUIRES ALL CONTINUOUS LOADS TO BE
 FIGURED AT 125%.
 PLEASE ADJUST LOAD CALCS IF NEEDED.
  
 10)NOTE: PLEASE SEE PREVIOUS REVIEW WITH
 RESPECT TO MIN CLEARENCES REQUIRED FOR
 CU DISC'S PER 110.26
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  