| 2005-12-19 00:00:00 | ******* UNSAT *********** |
| | |
| | |
| | PLEASE SEE SOME ITEMS REDLINED FROM |
| | PREVIOUS REVIEW(S). |
| | |
| | 1)NOTE: PLEASE SEE NFPA-70, NFPA-101 |
| | 210.70, 7.8 WHICH REQUIRES A MIN CONTROL |
| | AND EGRESS LIGHTING. |
| | PLEASE SEE MANY LOCATIONS ON PLANS WHICH |
| | ONLY INDICATE A J-BOX, WHERE A MIN |
| | LIGHTING SOURCE IS REQUIRED. |
| | |
| | 2)NOTE: PLEASE SEE MASTER BEDROM SD IS |
| | REQUIRED TO BE WITHIN 3' OF THE PEAK ON |
| | A SLOPED CEILING. |
| | NFPA-72 11.8.3.5 |
| | |
| | 3)NOTE: PLEASE SEE MIN LIGHTING,AND |
| | RECEPT(S) FOR AHU'S, 210.63,210.70 |
| | PLEASE ALSO VERIFY IF THE AHU ON FIRST |
| | FLR IS IN MASTER CLOSET, ALSO PLEASE |
| | VERIFY THE THERE IS NO OCP AT THIS |
| | DISCONNECT SHOWN ONPLANS. 240.24 |
| | 110.26 ETC. |
| | |
| | 4)NOTE: PLEASE SEE MIN GROUNDING |
| | ELECTRODE CONDUCTOR SHALL BE SIZED PER |
| | 250.66. 1/0 MIN |
| | SERVICE RISER HAS BEEN ADJUSTED. |
| | |
| | 5)NOTE: PLEASE ALSO SEE SERVICE IS NOW |
| | SHOWN AS 400A'S, HOWEVER SEC'S FROM |
| | METER TO FPL HANDHOLE IS ONLY RATED AT |
| | 200A'S. |
| | PLEASE SEE 310.15B6, 310.16 |
| | |
| | 6)NOTE: PLEASE VERIFY THE 2-200A |
| | BREAKERS SHOWN ON METER/MAIN SCHEDULE, |
| | PLEASE SEE BOTH DO NOT SEEM TO BE LISTED |
| | ONTHE SCHEDULE? ARE THESE ABOVE THE |
| | 6-SPACES? |
| | |
| | 7)NOTE: PLEASESEE POSSIBLE MISSING GFI |
| | FROM KITCHEN COUNTERSPACE. PLEASE SEE |
| | WHAT APPEARS TO BE 12" SPACE REDLINE DON |
| | PLANS. |
| | 210.52C1 |
| | |
| | 8)NOTE: PLEASE SEE RISER SHOWS POOL |
| | PANEL BEING FED FROM PANEL "B" , HOWEVER |
| | PANEL SCHEDULE "B" DOES NOT INCLUDE POOL |
| | PANEL, YET METER/MAIN SCHEDULE DOES. |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE INDICATE IF THE LOAD |
| | SHOWN FOR POOL PUMP IS ALEADY FIGURED |
| | FOR CONTINUOUS LOAD. ? |
| | PLEASE SEE 215.3, 230.42 ETC WHICH |
| | REQUIRES ALL CONTINUOUS LOADS TO BE |
| | FIGURED AT 125%. |
| | PLEASE ADJUST LOAD CALCS IF NEEDED. |
| | |
| | 10)NOTE: PLEASE SEE PREVIOUS REVIEW WITH |
| | RESPECT TO MIN CLEARENCES REQUIRED FOR |
| | CU DISC'S PER 110.26 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |