Plan Review Notes
Plan Review Notes For Permit 05030779
Permit Number 05030779
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-08 00:00:00*********** PROVISO ************
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
  
 1)NOTE: PLEASE INCLUDE ALL SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS. PLEASE SEE NONE WERE
 ADDED PER PREVIOUS COMMENTS.
 NFPA-72 11.5.1.1
  
 2)NOTE: PLEASE CLARIFY METER/MAIN COMBO.
 RISER APPEARS TO SHOW MENTION A MAIN,
 HOWEVER PLEASE BE SURE THIS EQUIPMENT
 DOES NOT CONTAIN ANY MORE THAN 6 MEANS
 OF DISCONNECT. 230.71
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 4)RELINED THE FOLLOWING
 110.26, CU DISC'S.
 210.70/ 101 7-9 EGRESS LIGHTING
 REQUIRED.
 210.63 AND 210.70 FOR LT RECEPT REQUIRED
 IN ATTIC SPACE.
  
 PLEASE REVISE THE ABOVE ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  