| Plan Review Notes For Permit 05030779 |
| Permit Number |
05030779 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-08 00:00:00 | *********** PROVISO ************ | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEWS. | | | | | | 1)NOTE: PLEASE INCLUDE ALL SMOKE | | | DETECTORS INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS. PLEASE SEE NONE WERE | | | ADDED PER PREVIOUS COMMENTS. | | | NFPA-72 11.5.1.1 | | | | | | 2)NOTE: PLEASE CLARIFY METER/MAIN COMBO. | | | RISER APPEARS TO SHOW MENTION A MAIN, | | | HOWEVER PLEASE BE SURE THIS EQUIPMENT | | | DOES NOT CONTAIN ANY MORE THAN 6 MEANS | | | OF DISCONNECT. 230.71 | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 4)RELINED THE FOLLOWING | | | 110.26, CU DISC'S. | | | 210.70/ 101 7-9 EGRESS LIGHTING | | | REQUIRED. | | | 210.63 AND 210.70 FOR LT RECEPT REQUIRED | | | IN ATTIC SPACE. | | | | | | PLEASE REVISE THE ABOVE ALONG WITH ANY | | | OTHER REVISIONS BEFORE ROUGH ELECTRICAL | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|